Chapter 4 Wiring

4-7

4

ENGLISH

4-3-3 Wiring to the MPCE Monitor Input Terminal

Two MPCEs are used in the machine control circuit. The MPCE monitor function monitors the operation of
MPCE1 and MPCE2 to detect control circuit errors and MPCE unit errors that prevent the transmission of the
OSSD output signal to the machine. When an error is detected, the SL-C Series and SL-R11E go to the
lockout condition. To enable this feature, it is necessary to set the mode switches of MPCE monitor to “En-
able” according in the instructions in section 2-11 “Mode Switch Settings” (

➮ page 2-5).

Use a device for the MPCE that has normally closed contacts and that has a maximum response delay time
of 292ms.

In addition, when connecting a MPCE to the MPCE monitor input terminal, the wiring is as shown below, so
refer to the example when wiring.

Wiring diagram

MPCE2

MPCE1

Start / Restart
input

TEST input

M/S SELECT
input

MPCE
MONITOR input

E-STOP1
input

E-STOP2
input

1.Wire the MPCE1 relay coil to OSSD1.

➮ For details, see page 4-1 “4-2 Method for Wiring to the Relay

Output Terminal” .

2.Wire the MPCE2 relay coil to OSSD2.

3.To enable the MPCE monitor, connect the MPCE1 normally closed contact and MPCE2 normally closed

contact in series, and then connect them to the MPCE monitor input terminal.

Timing chart

ON

OFF

ON

OFF

Clear

Blocked

OSSD

20ms Max.

292ms Max.

ON

OFF

ON

OFF

Clear

Blocked

OSSD

MPCE monitor
input

20ms Max.

292ms Max.

Lockout
condition

Lockout
condition

MPCE monitor
input

*

*

ON

OFF

ON

OFF

Clear

Blocked

OSSD

MPCE monitor
input

20ms Max.

292ms Max.

ON

OFF

ON

OFF

Clear

Blocked

OSSD

MPCE monitor
input

20ms Max.

292ms Max.

*

*

Timing chart when an error occurs

Timing chart when normal

* Depends on response time of machine’s MPCE