3 method for wiring to signal input terminals, English – KEYENCE SL-R11E User Manual
Page 30
Chapter 4 Wiring
4-4
4
English
ENGLISH
4-3 Method for Wiring to Signal Input Terminals
As shown in the table below, the SL-R11E is provided with a signal input terminal block. First loosen the
terminal block screws, and then retighten the terminal block screws after inserting the signal cables.
Input terminals
Terminal No.
Name
1, 2
Start / Restart input
3, 4 *
1
TEST input
5, 6 *
1
M/S SELECT input *
2
7, 8
MPCE MONITOR input
9, 10 *
1
E-STOP1 input
11, 12 *
1
E-STOP2 input
See Instruction Man
ual.
MPCE2
MPCE1
T R
POWER
FSD-ON
FSD-OFF
INTERLOCK
LOCKOUT
RESTART
TEST
MPCE
E-STOP1
E-STOP2
CAUTION
Electric shock
*1 Short bars are attached between 3 and 4, 5
and 6, 9 and 10, and 11 and 12 in the factory
default state. When using each function,
remove the short bars before performing wiring.
*2 Main/Sub select input
2
1
3
Tighten with flat-head
screwdriver
Insert wire
Loosen with flat-head
screwdriver
• Tightening torque
4.4 lb•in (0.5 N•m)
• Wire rating
AWG #22 to 14 (Stranded only, Copper only, min. 60 °C)
• Cable stripping dimension
10mm
(0.39")