beautypg.com

Carrier 50HCQ04---12 User Manual

Page 9

background image

9

Relative Humidity Sensor
(Polarized Male Connector)

J4-1 or J4-4 + 24 VDC Supply Voltage

J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output

to RTU-OPEN

4-20 VAC GND 0-5V
mA or or
VDC 0-10V

SPAN

ZERO

C10839

Fig. 9 -- Duct Relative Humidity Sensor Typical Wiring

To wire return air enthalpy sensor:

--MP

Connect the 4-20 mA In terminal on the enthalpy switch/

receiver to the 4-20 mA Out terminal on the return air

enthalpy sensor. Connect the 24-36 VDC Out terminal on

the enthalpy switch/receiver to the 24-36 VDC In terminal

on the return air enthalpy sensor. (See Fig 10.)

Fire Shutdown

The fire shutdown input is provided for unit shutdown in

response to a fire alarm or smoke detector. The fire

shutdown input is dedicated to input 5 and tells the

RTU-OPEN when to shutdown due to smoke detection or

fire alarm system.

The normal condition for fire

shutdown is there is no fire alarm. The unit may have

factory installed smoke detector(s); refer to the base unit

installation instructions for details on any adjustments

required during unit installation. Fire shutdown is always

factory configured for a normally open smoke detector.
For field installation of a smoke detector see instructions

for that specific accessory.

See below and the

troubleshooting section for wiring at the unit’s Low

Voltage Terminal Board (LVTB).

S

LVTB -- UNIT SHUTDOWN -- 24v OUT = 24 VAC
source

S

LVTB -- UNIT SHUTDOWN -- Smoke Alarm = Signal
input to RTU--OPEN

NOTE: Input 5 can also be wired into J5--3.

Filter Status

The filter status accessory is a field-installed accessory.

This accessory detects plugged filters. When installing

this accessory, the unit must have a free input (input 3, 5,

8, or 9). One of the dedicated functions (Humidistat, Fire

shutdown, Enthalpy, or Compressor safety) must not be in

use to configure Filter Status. Refer to the configuration

section for details on configuring inputs for specific

functions and state. Refer to Fig. 1 for wire terminations

at J5.

Fan Status

The fan status accessory is a field-installed accessory.

This accessory detects when the indoor fan is moving air.

When installing this accessory, the unit must have a free

input (input 3, 5, 8, or 9). One of the dedicated functions

(Humidistat, Fire shutdown, Enthalpy, or Compressor

safety) must not be in use to configure Fan Status. Refer

to the configuration section for details on configuring

inputs for specific functions and state. Refer to Fig. 1 for

wire terminations at J5.

Remote Occupancy

The remote occupancy accessory is a field-installed

accessory. This accessory provides an input to change the

units occupancy status. When installing this accessory, the

unit must have a free input (input 3, 5, 8, or 9). One of

the dedicated functions (Humidistat, Fire shutdown,

Enthalpy, or Compressor safety) must not be in use to

configure remote occupancy. Refer to the configuration

section for details on configuring inputs for specific

functions and state. Refer to Fig. 1 for wire terminations

at J5.

This manual is related to the following products: