APPENDIX A -- USER INTERFACE MENUS (CON’T)
Maintenance Menu
BACview MENU
POINT NAME
BACnet OBJECT
RANGE
FIELD ASSISTANT
MENU
HOME
Select function below
Properties/Equipment
MAINT
UNIT MAINTENANCE
Maintenance
Occupancy Status
occ_status
Occupied/Unoccupied
Space Temp Sensor
spt_status
1=Sensor Failure
2=SPT Sensor
3=T55/T56
4=Network
5=Airside Linkage
6=Locked Value
Setpoint Adjustment
stpt_adj
x ° F
System Cooling Demand Level
cool_demand_level
x
System Heating Demand Level
heat_demand_level
x
Safety Chain Feedback
safety_status
Off/Run Enabled
Fire Shutdown Status
firedown_status
Run Enabled/Shut-
down
Compressor Safety Status
comp_status
Normal/Trouble
Active Compressor Stages
comp_run
x
Active Heat Stages
heat_run
x
Enthalpy Status
enthalpy_status
High/Low
Humidistat Input Status
humstat_status
Low/High
Filter Status
filter_status
Clean/Dirty
Door Contact Status
door_contact_status
Off/On
Reset Supply Fan Runtime Alarm
sfan_rntm_clr
Run/Clear
Reset Comp 1 Runtime Alarm
comp1_rntm_clr
Run/Clear
Reset Comp 2 Runtime Alarm
comp2_rntm_clr
Run/Clear
Reset Filter Runtime Alarm
filter_rntm_clr
Off/On
OCCUPANCY MAINTENANCE
BAS On / Off
keypad_ovrde
1=Inactive
2=Occupied
3=Unoccupied
Schedule
schedule
Unoccupied/Occupied
Pushbutton Override
pb_status
Off/Active
Occupancy Contact
occ_contact_status
Off/On
Override Time Remaining
ovrde_time
xxx min
RUNTIME
Supply Fan Runtime
sfan_rntm
xxxxx
Compressor 1 Runtime
comp1_rntm
xxxxx
Compressor 2 Runtime
comp2_rntm
xxxxx
Filter Runtime
filter_rntm
xxxxx