APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)

(IN ALPHABETICAL ORDER)

BACnet

Modbus

N2

LON Works

Point Name

Read/

Write

BACnet Point

Name

OBJECT

ID

Register

Type

Register

#

Network

Point

Type

Network

Point

Address

SNVT Type

SNVT Name

Input 1 Function

R/W

ai1_function

MSV:8100

1

Input 2 Function

R/W

ai2_function

MSV:8100

2

Input 3 Function

R/W

di3_function

MSV:8100

3

Input 3 Switch Con-

figuration

R/W

di3_type

MSV:8101

3

Input 5 Function

R/W

di5_function

MSV:8100

5

Input 5 Switch Con-

figuration

R/W

di5_type

MSV:8101

5

Input 8 Function

R/W

di8_function

MSV:8100

8

Input 8 Switch Con-

figuration

R/W

di8_type

MSV:8101

8

Input 9 Function

R/W

di9_function

MSV:8100

9

Input 9 Switch Con-

figuration

R/W

di9_type

MSV:8101

9

input_1

R

ai_1

AI:1001

input_10

R

ai_10

AI:1010

input_11

R

ai_11

AI:1011

input_2

R

ai_2

AI:1002

input_3

R

di_3

BI:1003

input_4

R

di_4

BI:1004

input_5

R

di_5

BI:1005

input_7

R

ai_7

AI:1007

input_8

R

di_8

BI:1008

input_9

R

di_9

BI:1009

Low Space Relative

Humidity

R

sprh_lo_alarm

BV:7019

discrete

in

10038

BI

38

SNVT_switch

(95)

nvoLoS-

PRHAlm

Low Space Temp

Alarm

R

spt_lo_alarm

BV:7012

discrete

in

10039

BI

39

SNVT_switch

(95)

nvo-

LoSpaceTemp

Low Supply Air Tem-

perature

R

sat_lo_alarm

BV:7021

discrete

in

10040

BI

40

SNVT_switch

(95)

nvoLoSATAlm

Maximum Heating

SAT

R/W

sat_ht_max

AV:83004

Min Setpoint Separa-

tion

R/W

min_stpt_sep

AV:63

Minimum Cooling

SAT

R/W

sat_cl_min

AV:83003

OAQ Sensor

R

oaq_alarm

BV:7006

discrete

in

10041

BI

41

SNVT_switch

(95)

nvoOAQSens

or

Occ Relative Humid-

ity Setpoint

R/W

occ_de-

hum_stpt

AV:3011

float

value

40083

ADF

36

SNVT_lev_per-

cent (81)

nviOccRHSP

Occupancy Contact

R

occ_con-

tact_status

BV:1007

Occupancy Source

R/W

occ_source

MSV:1002

Occupancy Status

R

occ_status

BV:2008

discrete

in

10018

BI

18

SNVT_switch

(95)

nvoOccStatus

Operating Mode

R

run_status

MSV:2002

un-

signed

int

30001

ADI

13

SNVT_count_inc

(9)

nvoOperating-

Mode

Optimal Start

R/W

optm_start

AV:9026

float

value

40147

ADF

61

SN-

VT_time_hour

(124)

nviOptimal-

Start

Outdoor Air CO2

R

oaq

AV:1010

float

value

40085

ADF

37

SNVT_ppm (29)

nvoOAQ

Outdoor Air Temp

Sensor Alarm

R

oat_alarm

BV:7003

Outdoor Air Temper-

ature

R

oa_temp

AV:1003

float

value

40087

ADF

38

SNVT_temp_p

(105)

nvoOAT

Outdoor CO2 Sensor

Value @ Max mA

R/W

oaq_ref_hi_pp

m

AV:9014

Outdoor CO2 Sensor

Value @ Min mA

R/W

oaq_ref_lo_pp

m

AV:9013