Configuration points (con’t) – Carrier 50HCQ04---12 User Manual
Page 43
43
CONFIGURATION POINTS (CON’T)
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE
DEFAULT
ENTRY
HOME
Select function below
CONFIG
CONFIGURATION
INPUT
INPUT CONFIGURATION
Input 1 Function
ai1_function
1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH
Sensor
No Sensor
Input 2 Function
ai2_function
1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH
Sensor
1 (No FIOP)
2 (FIOP)
Input 3 Function
di3_function
1=No Function
2=Compressor
Safety
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
Compressor Safety
Input 3 Switch Configuration
di3_type
N/O
N/C
N/O
Input 5 Function
di5_function
1=No Function
2=Fire Shutdown
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
Fire Shutdown
Input 5 Switch Configuration
di5_type
N/O
N/C
N/O
Input 8 Function
di8_function
1=No Function
2=Enthalpy Switch
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
1 (No FIOP)
2 (FIOP)
Input 8 Switch Configuration
di8_type
N/O
N/C
N/O
Input 9 Function
di9_function
1=No Function
2=Humidistat
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
Humidistat
Input 9 Switch Configuration
di9_type
N/O
N/C
N/O
Space sensor type
spt_type
1=T55
2=T56 (use for T59)
3=SPT Sensor
T55
T5x Override Duration
ovr_dur
0---24 hours
1