beautypg.com

Operation – Carrier 50HCQ04---12 User Manual

Page 17

background image

17

USERPW

This submenu screen allows you to change the user

password to a four number password of choice. The User

password change screen is only accessible with the

Administrator Password (1111). The ADMIN password

will always override the user password.

Factory Default = 0000

Range = 0000--9999

OPERATION

The RTU-OPEN will control the compressors, economizer

and heating outputs based on its space temperature input

and setpoints. It can also be controlled by a building

control system or zoning system. An optional CO

2

IAQ

sensor mounted in the space can influence the economizer

minimum position. The RTU-OPEN has a hardware clock

that can allow scheduling for stand-alone operation. The

RTU-OPEN’s default is to control to occupied setpoints

all the time, until a type of occupancy control is set. The

following sections describe the operation for the functions

of the RTU-OPEN.

Occupancy

Occupancy is the fundamental overall control of

equipment.

The unit can be in one of two states:

Occupied or Unoccupied. These are usually referred to as

periods because they represent periods of any given day.

Before RTU-OPEN can operate specific functions of the

equipment it is installed on, occupancy must be

determined. There are four different ways RTU-OPEN

can determine occupancy. These are described below and

selected by the configuration point Occupancy Source.

Always Occupied (Default)

The unit will not determine occupancy and continuously

run in the occupied state or period. RTU-OPEN ships from

the factory with this setting to allow immediate operation.

BACnet Schedule

When Occupancy Source is set to BACnet Schedule,

RTU-OPEN will use a schedule to change occupancy

based upon a day of week and a time period. Local time

and date should be set in the RTU-OPEN for this function

to operate properly. This function applies if setting a local

schedule in the RTU-OPEN or if applying the unit to an

I-Vu Open network or an OPEN zoning system.

An

OPEN network schedule can override a local schedule

within the unit. A space sensor push button override is

only available when running a local or OPEN schedule.

The push button will override an unoccupied period to

occupied for the specified time duration.

BAS On/Off

When Occupancy Source is set to BAS On/Off,

RTU-OPEN follows occupancy based on an On/Off

command to the BAS ON/OFF software point. An on

command sets the occupancy to occupied, and an off

command sets it to unoccupied. The Building Automation

System can be speaking BACnet, Modbus, N2, or LON

and is writing to the BAS On/Off point in the open

protocol point map.

Remote Occ Input

When Occupancy Source is set to Remote Occ Input,

RTU-OPEN follows occupancy based on the remote

occupancy switch input. Inputs 3, 5, 8, and 9 on plug J5

can be hard-wired to command the unit’s occupancy. The

Occupancy Contact point show the status as on or off, on

is occupied and off is unoccupied.

Indoor (Supply) Fan

The indoor fan can be configured to operate in three

different manors.

The configuration point Fan Mode

determines how the fan will run. The fan will always be

disabled if a fire shutdown or safety chain alarm is active.

A valid space temperature and supply air temperature

must be available for the fan to operate. There is a unit

start delay in effect when the unit is transitioning from

unoccupied to occupied. The following describes specific

fan operation based on the Fan Mode configuration value.

Auto

When Fan Mode is set to Auto, RTU-OPEN will cycle the

fan on and off based on the demand for heating, cooling,

and dehumidification. There is a configurable fan off

delay that is upheld before shutting the fan off after

conditioning has ended.

Continuous

When Fan Mode is set to Continuous, RTU-OPEN will

cycle the fan based on occupancy. The fan will run the

whole occupied period and operate in the auto mode

during the unoccupied period.

Always On

When Fan Mode is set to Always On, RTU-OPEN will run

the fan all the time regardless of occupancy or demand.
The RTU-OPEN has an optional Supply Fan Status input

to provide proof of airflow. If this is enabled, the point

will look for a contact change whenever the Supply Fan

Relay is on. If it is not enabled then it will always be the

same state as the Supply Fan Relay. The cooling,

economizer, heating, dehumidification, CO

2

and power

exhaust routines will use this input point for fan status.

This manual is related to the following products: