beautypg.com

Carrier 50HCQ04---12 User Manual

Page 20

background image

20

Optimal Start

The RTU--OPEN may utilize Optimal Start, which adjusts

the effective setpoints to achieve the occupied setpoints

by the time scheduled occupancy begins. The Optimal

Start recovery period may begin as early as 4 hours prior

to occupancy. The algorithm works by moving the

unoccupied setpoints toward the occupied setpoints. The

rate at which the setpoints move is based on the outside

air temperature, design temperatures, and capacities. The

following conditions must be true for unoccupied free

cooling to operate:

S

Under SETPOINT, Optimal Start Value must be set
greater than zero and less than or equal to four (0
disables Optimal Start.)

S

The system is unoccupied

S

The RTU--OPEN has a valid outside air temperature

S

The RTU--OPEN is running occupancy based on a
schedule, were next time occupied is known.

Fire Shutdown

Fire Shutdown may be configured on Binary Input 5. A

typical application involves a smoke detector or fire

shutdown contact, which, when active, immediately shuts

down equipment operation.

Compressor Safety

Compressor Safety may be configured on Binary Input 3.

A compressor safety tripped indicator circuit is available

on most Carrier rooftop equipment. A Compressor Safety

Alarm indicates that the equipment requires attention.

Cooling, heating, and supply fan outputs are not

interrupted except where the RTU--OPEN is configured

for Heat Pump operation. When configured for Heat

Pump, and in the heating mode, a compressor safety fault

will cause the available stages of electric heating to be

enabled in place of mechanical heating. Normal operation

resumes when the compressor safety circuit is

de--energized.

Fan Status

Fan Status may be configured on any unused binary input

channel. A typical application would be an airflow switch,

current sensing relay, or other device that provides a

supply fan running verification. Enabling this function

displays the supply fan’s status on the equipment graphic.

If the controller loses fan status during operation, heating

and cooling are disabled, the economizer damper (if

available) is closed, and an alarm for loss of status is

indicated. If the fan status is on when the controller is

commanding the fan off, the unit remains in the off state.

An alarm is generated indicating that the fan is running

when it should be off.

Filter Status

Filter status may be configured on any unused binary

input channel. A typical application is a differential

pressure switch that senses the pressure drop across a filter

bank. When the pressure across the filter bank exceeds the

setpoint of the differential pressure switch, the Filter

status is displayed as Dirty on the controller graphic. An

alarm indicates a dirty filter.

Door Switch

A Door Contact may be configured on any unused binary

input. A typical application is an occupancy sensor

mounted within the space served by a single zone rooftop.

Door Contact disables mechanical cooling and electric or

gas heating, when active. Economizer cooling, if

available, continues to operate.

Linkage

The RTU--OPEN may serve as an air source to an OPEN

Variable Volume Terminal (VVT) system. When the

RTU--OPEN is part of a VVT system and the controllers

are wired together to form a network, the controllers may

use a method of communication known as Linkaget.

Linkage is a method by which an air source and its

subordinate zone terminals exchange data to form a

coordinated HVAC system. The system’s air source

controller, zone controllers, and bypass controller are

linked so that their data exchange can be managed by one

zone controller configured as the VVT Master. The VVT

Master gathers the following information from the slave

zone controllers:

S

occupancy status

S

setpoints

S

zone temperature

S

relative humidity

S

CO

2

level

S

damper position

S

optimal start data

The VVT Master performs mathematical calculations and

algorithms on the data and then sends the composite

information to the air source. The VVT Master receives

information from the air source such as mode, supply air

temperature, and outside air temperature, and passes that

information to all linked controllers.

Linkage Air Source Modes

In a linked system, the air source determines its operating

mode and qualifies that mode based on its own Supply Air

Temperature (SAT). The following modes can be sent by

the air source depending on its configuration:

S

Off – Air source fan is off

S

Fan Only – Air source fan is on and providing
ventilation (neutral SAT) without heating or cooling

S

Economizer Cooling – Air source fan is on and
providing cooling, using economizer only

S

Cooling – Air source fan is on and cooling is provided
by economizer and mechanical cooling

S

Heating – Air source fan is on and heating is provided
(gas or electric)

S

Dehumidification – Air source fan is on and
Humidi--MiZer] is active

S

Test – The RTU Open Service Test mode is active

S

Shutdown – Air source fan is off due to Safety Chain,
Fire Shutdown, or invalid SAT sensor

S

Unocc Free Cooling – Air source fan is on, with the
economizer providing cooling while unoccupied

This manual is related to the following products: