Carrier 50HCQ04---12 User Manual
Page 40
40
APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)
(IN ALPHABETICAL ORDER)
BACnet
Modbus
N2
LON Works
Point Name
Read/
Write
BACnet Point
Name
OBJECT
ID
Register
Type
Register
#
Network
Point
Type
Network
Point
Address
SNVT Type
SNVT Name
Supply Air Temp
Sensor
R
sat_alarm
BV:7004
discrete
in
10047
BI
47
SNVT_switch
(95)
nvoSAT-
Sensor
Supply Air Temperat-
ure
R
sa_temp
AV:1008
float
value
40109
ADF
49
SNVT_temp_p
(105)
nvoSAT
Supply Fan Failure
R
sfan_fail_alar
m
BV:7008
Supply Fan in Hand
R
sfan_hand_ala
rm
BV:7009
Supply Fan Relay
State
R
sfan
BV:2001
discrete
in
10023
BI
23
SNVT_switch
(95)
nvoSFRelay
Supply Fan Runtime
R
sfan_rntm
AV:2014
Supply Fan Runtime
R
sfan_rntm_ala
rm
BV:7010
Supply Fan Service
Alarm Timer
R/W
sfan_ser-
vice_hrs
AV:83005
Supply Fan Status
R
sfan_status
BV:1003
discrete
in
10024
BI
24
SNVT_switch
(95)
nvoFanStatus
Switch Configuration
R
di_cfg_alarm
BV:7025
System Cooling De-
mand Level
R
cool_de-
mand_level
AV:9006
System Heating De-
mand Level
R
heat_de-
mand_level
AV:9036
System is shut down
R
shut-
down_status
BV:2011
System Mode
R
mode_status
MSV:2001
System OAT Master
R
mstr_oa_temp
AV:80001
System Outdoor Air
Temperature
R/W
system_oat
AV:1901
float
value
40119
ADF
54
SNVT_temp_p
(105)
nviSysOAT
System Space Tem-
perature
R/W
system_spt
AV:1902
float
value
40123
ADF
56
SNVT_temp_p
(105)
nviSysSpaceT
emp
T5x Override Dura-
tion
R/W
ovr_dur
AV:9023
Unit Start Delay
R/W
start_delay
AV:9007
float
value
40127
ADF
58
SNVT_time_sec
(107)
nviUnit-
StartDly
Unit Type
R/W
unit_type
MSV:9018
Unocc Free Cool En-
able
R/W
ntfc_ena
BV:80001
Unocc Relative Hu-
midity Setpoint
R/W
unocc_de-
hum_stpt
AV:3012
float
value
40129
ADF
59
SNVT_lev_per-
cent (81)
nviUnoc-
cRHSP
Vent Dmpr Pos /
DCV Min Pos
R/W
econ_min
AV:9005
float
value
40131
ADF
60
SNVT_lev_per-
cent (81)
nviDCVMin-
Pos