APPENDIX B -- THIRD PARTY POINTS LIST
(IN ALPHABETICAL ORDER)
BACnet
Modbus
N2
LON Works
Point Name
Read/
Write
BACnet Point
Name
OBJECT
ID
Register
Type
Register
#
Network
Point
Type
Network
Point
Address
SNVT Type
SNVT Name
Active Compressor
Stages
R
comp_run
AV:2020
float
value
40031
ADF
10
SNVT_count_inc
(9)
nvo-
CompStages
Active Heat Stages
R
heat_run
AV:2003
float
value
40033
ADF
11
SNVT_count_inc
(9)
nvoHeat
Stages
Airside Linkage
Alarm
R
air_link-
age_fail
BV:7030
Analog Input Config-
uration
R
ai_cfg_alarm
BV:7026
BAS On / Off
R/W
keypad_ovrde
MSV:1001
un-
signed
int
40133
ADI
1
SNVT_count_inc
(9)
nviBASOnOff
Compressor 1 Relay
State
R
comp_1
BV:2005
Compressor 1
Runtime
R
comp1_rntm
AV:2017
Compressor 1
Runtime
R
comp1_rntm_
alarm
BV:7014
Compressor 1 Ser-
vice Alarm Timer
R/W
comp1_ser-
vice_hrs
AV:83006
Compressor 1 Test
R/W
comp1_test
BV:81005
Compressor 2 Relay
State
R
comp_2
BV:2004
Compressor 2
Runtime
R
comp2_rntm
AV:2018
Compressor 2
Runtime
R
comp2_rntm_
alarm
BV:7015
Compressor 2 Ser-
vice Alarm Timer
R/W
comp2_ser-
vice_hrs
AV:83007
Compressor 2 Test
R/W
comp2_test
BV:81004
Compressor Safety
R
comp_alarm
BV:7013
discrete
in
10030
BI
30
SNVT_switch
(95)
nvo-
CompSafety
Compressor Safety
Status
R
comp_status
BV:1008
Continuous Occu-
pied Exhaust
R/W
occ_exh
BV:9002
Cooling Lockout
Temperature
R/W
oat_cl_lockout
AV:9002
float
value
40043
ADF
16
SNVT_temp_p
(105)
nviCoolLck-
Temp
DCV Max Ctrl Set-
point
R/W
iaq_stpt_max
AV:3013
float
value
40045
ADF
17
SNVT_ppm (29)
nviD-
CVMaxPPM
DCV Max Vent
Damper Pos
R/W
iaq_dpr_max
AV:9011
float
value
40047
ADF
18
SNVT_lev_per-
cent (81)
nviDCVMax-
Pos
Dehumidification Re-
lay State
R
dehum
BV:2006
discrete
in
10009
BI
9
SNVT_switch
(95)
nvoDehumRe-
lay
Dehumidification Test
R/W
dehum_test
BV:81006
Door Contact Status
R
door_con-
tact_status
BV:1010
Economizer Exists
R/W
econ_exist
BV:99001
Economizer High
OAT Lockout Temp
R/W
oat_ec_lock-
out
AV:9008
Economizer Output
R
econ_output
AV:2001
float
value
40051
ADF
20
SNVT_lev_per-
cent (81)
nvoEconOut-
put
Economizer Test
R/W
econ_test
AV:81001
Effective Cool Set-
point
R
eff_cl_stpt
AV:3005
float
value
40055
ADF
22
SNVT_temp_p
(105)
nvoEffCoolSP
Effective Heat Set-
point
R
eff_ht_stpt
AV:3006
float
value
40057
ADF
23
SNVT_temp_p
(105)
nvoEffHeatSP
Enthalpy (BACnet)
R/W
oae
BV:1901
Enthalpy Status
R
en-
thalpy_status
BV:1002
Factory Test
R/W
fac_test_en-
able
BV:91000
Factory Test Analog
1 Control
R/W
ao1_fac_test
AV:91001
Factory Test Analog
2 Control
R/W
ao2_fac_test
AV:91002