beautypg.com

Appendix a -- user interface menus (con’t), Configuration menus (con’t) – Carrier 50HCQ04---12 User Manual

Page 33

background image

33

APPENDIX A -- USER INTERFACE MENUS (CON’T)

Configuration Menus (con’t)

BACview MENU

POINT NAME

BACnet

OBJECT

RANGE

DEFAULT

FIELD ASSISTANT MENU

HOME

Select function below

Properties/Equipment

SERVICE

SERVICE CONFIGURATION

Service Configuration

Unit Type

unit_type

1=Heat/Cool

2=HP O/B Ctrl

3=HP Y1/W1

Ctrl

Heat/Cool (TC and

HC models)

HP Y1/W1 Ctrl

(TCQ and HCQ

models)

Compressor Stages

comp_stages

One stage/ Two

Stage

One Stage (sizes

04---07, and

A08---A12)

Two Stages (sizes

08---30)

Economizer Exists

econ_exist

No/Yes

No (No FIOP)

Yes (FIOP)

Reversing Valve Type

rev_vlv_type

O output type/B

output type

O output type

Heat Type

heat_type

Electric/Gas

Gas (48 Series

Units)

Electric (50 Series

Units)

Number of Heat Stages

heat_stages

1 / 2 / 0 (no

heat)

0 (50 series cool-

ing only units)

1 (All TCQs and

HCQs, Low Nox

units, single phase

gas units,

TC04---09 low and

TC05---07 med

heat 3 phase gas

units)

2 (TC04 and

08---09 med,

TC05---09 high

heat 3 phase gas

units, HC04---09 3

phase gas units

and All 12---30 gas

units)

Continuous Occupied Exhaust

occ_exh

No/Yes

No

Indoor CO2 Sensor Value @

Min mA

iaq_ref_lo_ppm

0---9999ppm

0

Indoor CO2 Sensor Value @

Max mA

iaq_ref_hi_ppm

0---9999ppm

2000

Outdoor CO2 Sensor Value @

Min mA

oaq_ref_lo_ppm

0---9999ppm

0

Outdoor CO2 Sensor Value @

Max mA

oaq_ref_hi_ppm

0---9999ppm

2000

(Field Assistant Only)

System Space Temperature

system_spt

System Cooling Demand Level

cool_de-

mand_level

0---3

0

System Heating Demand Level

heat_de-

mand_level

0---3

0

System Outdoor Air Temperat-

ure

system_oat

TEST

SERVICE TEST

Service Test

test_enable

Disable/Enable

Disable

Fan Test

fan_test

Disable/Enable

Disable

Compressor 1 Test

comp1_test

Disable/Enable

Disable

Compressor 2 Test

comp2_test

Disable/Enable

Disable

Heat 1 Test

heat1_test

Disable/Enable

Disable

Heat 2 Test

heat2_test

Disable/Enable

Disable

Reversing Valve Test

rev_vlv_test

Disable/Enable

Disable

Dehumidification Test

dehum_test

Disable/Enable

Disable

Power Exhaust Test

pexh_test

Disable/Enable

Disable

Economizer Test

econ_test

0---100 %Open

0

Analog Output 2 Test

ao2_test

0---100 %

0