Appendix a -- user interface menus (con’t), Configuration menus (con’t) – Carrier 50HCQ04---12 User Manual
Page 33
33
APPENDIX A -- USER INTERFACE MENUS (CON’T)
Configuration Menus (con’t)
BACview MENU
POINT NAME
BACnet
OBJECT
RANGE
DEFAULT
FIELD ASSISTANT MENU
HOME
Select function below
Properties/Equipment
SERVICE
SERVICE CONFIGURATION
Service Configuration
Unit Type
unit_type
1=Heat/Cool
2=HP O/B Ctrl
3=HP Y1/W1
Ctrl
Heat/Cool (TC and
HC models)
HP Y1/W1 Ctrl
(TCQ and HCQ
models)
Compressor Stages
comp_stages
One stage/ Two
Stage
One Stage (sizes
04---07, and
A08---A12)
Two Stages (sizes
08---30)
Economizer Exists
econ_exist
No/Yes
No (No FIOP)
Yes (FIOP)
Reversing Valve Type
rev_vlv_type
O output type/B
output type
O output type
Heat Type
heat_type
Electric/Gas
Gas (48 Series
Units)
Electric (50 Series
Units)
Number of Heat Stages
heat_stages
1 / 2 / 0 (no
heat)
0 (50 series cool-
ing only units)
1 (All TCQs and
HCQs, Low Nox
units, single phase
gas units,
TC04---09 low and
TC05---07 med
heat 3 phase gas
units)
2 (TC04 and
08---09 med,
TC05---09 high
heat 3 phase gas
units, HC04---09 3
phase gas units
and All 12---30 gas
units)
Continuous Occupied Exhaust
occ_exh
No/Yes
No
Indoor CO2 Sensor Value @
Min mA
iaq_ref_lo_ppm
0---9999ppm
0
Indoor CO2 Sensor Value @
Max mA
iaq_ref_hi_ppm
0---9999ppm
2000
Outdoor CO2 Sensor Value @
Min mA
oaq_ref_lo_ppm
0---9999ppm
0
Outdoor CO2 Sensor Value @
Max mA
oaq_ref_hi_ppm
0---9999ppm
2000
(Field Assistant Only)
System Space Temperature
system_spt
System Cooling Demand Level
cool_de-
mand_level
0---3
0
System Heating Demand Level
heat_de-
mand_level
0---3
0
System Outdoor Air Temperat-
ure
system_oat
TEST
SERVICE TEST
Service Test
test_enable
Disable/Enable
Disable
Fan Test
fan_test
Disable/Enable
Disable
Compressor 1 Test
comp1_test
Disable/Enable
Disable
Compressor 2 Test
comp2_test
Disable/Enable
Disable
Heat 1 Test
heat1_test
Disable/Enable
Disable
Heat 2 Test
heat2_test
Disable/Enable
Disable
Reversing Valve Test
rev_vlv_test
Disable/Enable
Disable
Dehumidification Test
dehum_test
Disable/Enable
Disable
Power Exhaust Test
pexh_test
Disable/Enable
Disable
Economizer Test
econ_test
0---100 %Open
0
Analog Output 2 Test
ao2_test
0---100 %
0