CONFIGURATION POINTS (CON’T)

BACview

MENU

POINT NAME

BACnet

OBJECT

RANGE

DEFAULT

ENTRY

HOME

Select function below

CONFIG

CONFIGURATION

SERVICE

SERVICE CONFIGURATION

Unit Type

unit_type

1=Heat/Cool

2=HP O/B Ctrl

3=HP Y1/W1 Ctrl

Heat/Cool (TC and HC

models)

HP Y1/W1 Ctrl (TCQ

and HCQ models)

Compressor Stages

comp_stages

One stage/ Two

Stage

One Stage (sizes

04---07, and A08---A12)

Two Stages (sizes

08---30)

Economizer Exists

econ_exist

No/Yes

No (No FIOP)

Yes (FIOP)

Reversing Valve Type

rev_vlv_type

O output type/B

output type

O output type

Heat Type

heat_type

Electric/Gas

Gas (48 Series Units)

Electric (50 Series

Units)

Number of Heat Stages

heat_stages

1 / 2 / 0 (no heat)

0 (50 series cooling

only units)

1 (All TCQs and HCQs,

Low Nox units, single

phase gas units,

TC04---09 low and

TC05---07 med heat 3

phase gas units)

2 (TC04 and 08---09

med, TC05---09 high

heat 3 phase gas units,

HC04---09 3 phase gas

units and All 12---30

gas units)

Continuous Occupied Exhaust

occ_exh

No/Yes

No

Indoor CO2 Sensor Value @ Min mA

iaq_ref_lo_ppm

0---9999ppm

0

Indoor CO2 Sensor Value @ Max mA

iaq_ref_hi_ppm

0---9999ppm

2000

Outdoor CO2 Sensor Value @ Min

mA

oaq_ref_lo_ppm

0---9999ppm

0

Outdoor CO2 Sensor Value @ Max

mA

oaq_ref_hi_ppm

0---9999ppm

2000