APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)
(IN ALPHABETICAL ORDER)
BACnet
Modbus
N2
LON Works
Point Name
Read/
Write
BACnet Point
Name
OBJECT
ID
Register
Type
Register
#
Network
Point
Type
Network
Point
Address
SNVT Type
SNVT Name
Factory Test Relay 1
Control
R/W
re-
lay1_fac_test
BV:91001
Factory Test Relay 2
Control
R/W
re-
lay2_fac_test
BV:91002
Factory Test Relay 3
Control
R/W
re-
lay3_fac_test
BV:91003
Factory Test Relay 4
Control
R/W
re-
lay4_fac_test
BV:91004
Factory Test Relay 5
Control
R/W
re-
lay5_fac_test
BV:91005
Factory Test Relay 6
Control
R/W
re-
lay6_fac_test
BV:91006
Factory Test Relay 7
Control
R/W
re-
lay7_fac_test
BV:91007
Factory Test Relay 8
Control
R/W
re-
lay8_fac_test
BV:91008
Fan Off Delay
R/W
fan_delay_off
AV:9024
Filter
R
filter_alarm
BV:7017
discrete
in
10031
BI
31
SNVT_switch
(95)
nvoFilter
Filter Runtime
R
filter_rntm
AV:2015
Filter Service Alarm
Timer
R/W
filter_ser-
vice_hrs
AV:2019
float
value
40067
ADF
28
SN-
VT_time_hour
(124)
nviFilter-
AlmTime
Filter Status
R
filter_status
BV:1004
Fire Shutdown
R
fire_alarm
BV:7007
discrete
in
10032
BI
32
SNVT_switch
(95)
nvoFireShut-
down
Fire Shutdown
Status
R
fire-
down_status
BV:1005
Heat Stage 1 Relay
State
R
heat_1
BV:2003
Heat Stage 2 Relay
State
R
heat_2
BV:2002
Heating Lockout
Temperature
R/W
oat_ht_lock-
out
AV:9003
float
value
40069
ADF
29
SNVT_temp_p
(105)
nviHeatLck-
Temp
High CO2
R
co2_alarm
BV:7016
discrete
in
10033
BI
33
SNVT_switch
(95)
nvoHiCO2Alm
High Space Relative
Humidity
R
sprh_hi_alarm
BV:7018
discrete
in
10034
BI
34
SNVT_switch
(95)
nvoHiS-
PRHAlm
High Space Temp
Alarm
R
spt_hi_alarm
BV:7011
discrete
in
10035
BI
35
SNVT_switch
(95)
nvoHiS-
paceTemp
High Supply Air Tem-
perature
R
sat_hi_alarm
BV:7020
discrete
in
10036
BI
36
SNVT_switch
(95)
nvoHiSATAlm
HP Rev Cycle Lock-
out Temp
R/W
hp_rev_cycle_
lockout
AV:9004
float
value
40071
ADF
30
SNVT_temp_p
(105)
nviPRevClck-
Temp
Humidistat Input
Status
R
hum-
stat_status
BV:1006
IAQ Sensor
R
iaq_alarm
BV:7005
discrete
in
10037
BI
37
SNVT_switch
(95)
nvoIAQSensor
Indoor Air CO2
R
iaq
AV:1009
float
value
40073
ADF
31
SNVT_ppm (29)
nvoIAQ
Indoor CO2 Sensor
Value @ Max mA
R/W
iaq_ref_hi_pp
m
AV:9010
Indoor CO2 Sensor
Value @ Min mA
R/W
iaq_ref_lo_pp
m
AV:9009