Carrier 50HCQ04---12 User Manual
Page 23
23
Table 4 – RTU--OPEN Alarms
POINT NAME
BACnet Object
NAME
ACTION TAKEN BY
CONTROL
RESET METHOD
PROBABLE CAUSE
Safety Chain
safety_alarm
Immediate Shutdown
Automatic
Over load Indoor Fan or Electric
Heater overheat
Fire Shutdown
fire_alarm
Immediate Shutdown
Automatic
Smoke detected by smoke de-
tector or configuration incorrect
Supply Fan Failure
sfan_fail_alarm
Immediately disable
Operation
Automatic
Tripped Circuit Breaker, Broken
belt, Bad indoor fan motor, Con-
figuration incorrect, Bad fan
status switch.
Supply Fan in Hand
sfan_hand_alarm
Ramp down Operations
Automatic
Bad Fan Status Switch, Configur-
ation incorrect.
Compressor Safety
comp_alarm
Alert Generated
Automatic
Compressor would not start
Space Temp Sensor
spt_fail
Ramp down Operations
Automatic
Faulty, shorted, or open thermis-
tor caused by wiring error or
loose connection.
Supply Air Temp
Sensor
sat_alarm
Economizer Disabled
Automatic
Faulty, shorted, or open thermis-
tor caused by wiring error or
loose connection.
Outdoor Air Temp
Sensor Alarm
oat_alarm
Economizer and Low ambient
DX cooling lockout disabled.
Automatic
Faulty, shorted, or open thermis-
tor caused by wiring error or
loose connection.
Space Relative
Humidity Sensor
sprh_alarm
Dehumidification disabled
Automatic
Sensor reading is out of range.
Bad sensor, bad wiring, or sensor
configured incorrectly.
IAQ Sensor
iaq_alarm
No IAQ Operation
Automatic
Sensor reading is out of range.
Bad sensor, bad wiring, or sensor
configured incorrectly.
OAQ Sensor
oaq_alarm
Set OAQ to 400
Automatic
Sensor reading is out of range.
Bad sensor, bad wiring, or sensor
configured incorrectly.
Space Temperature
spt_alrm_status
Alert Generated
Automatic
Space value is less then the low
allowed value or Space value is
greater then the high allowed
value
Alarming
Temperature
spt_alrm_temp
Shows temperature that
caused alarm
N/A
N/A
Alarm Limit
Exceeded
spt_alrm_lmt
Shows the limit that was ex-
ceeded
N/A
N/A
High Supply Air
Temperature
sat_hi_alarm
Alert Generated
Automatic
SAT is greater then the configura-
tion for more then 5 minutes
Low Supply Air
Temperature
sat_lo_alarm
Alert Generated
Automatic
SAT is less then the configuration
for more then 5 minutes
Setpoint Slider
slidepot_alarm
Set Offset to zero
Automatic
STO sensor is open for more then
5 seconds
Switch Configuration
di_cfg_alarm
Disable only wrong switch
functions
Configure correctly
More then one discrete input is
configured to provide the same
function.
Analog Input
Configuration
ai_cfg_alarm
Disable 4 selectable analog
inputs
Configure correctly
More then one analog input is
configured to provide the same
function.
High Space Relative
Humidity
sprh_hi_alarm
Alert Generated
Automatic
IRH is greater then the configura-
tion for more then 15 minutes
Low Space Relative
Humidity
sprh_lo_alarm
Alert Generated
Automatic
IRH is less then the configuration
for more then 5 minutes
High CO2
co2_alarm
Alert Generated
Automatic
CO2 reading is above the config-
uration for 1 minute
Supply Fan Runtime
sfan_rntm_alarm
Alert Generated
zero the timer
Supply fan run time exceeded
user defined limit
Compressor 1 Runtime
comp1_rntm_alar
m
Alert Generated
zero the timer
Compressor run time limit is ex-
ceeded
Compressor 2 Runtime
comp2_rntm_alar
m
Alert Generated
zero the timer
Compressor run time limit is ex-
ceeded
Filter
filter_alarm
Alert Generated
Automatic / reset
timer
Dirty Filter, supply fan run time ex-
ceeded, filter switch configuration
wrong.
Airside Linkage Alarm
air_linkage_fail
Alert Generated
Automatic
Linkage communication failed