Table 4 – RTU--OPEN Alarms

POINT NAME

BACnet Object

NAME

ACTION TAKEN BY

CONTROL

RESET METHOD

PROBABLE CAUSE

Safety Chain

safety_alarm

Immediate Shutdown

Automatic

Over load Indoor Fan or Electric

Heater overheat

Fire Shutdown

fire_alarm

Immediate Shutdown

Automatic

Smoke detected by smoke de-

tector or configuration incorrect

Supply Fan Failure

sfan_fail_alarm

Immediately disable

Operation

Automatic

Tripped Circuit Breaker, Broken

belt, Bad indoor fan motor, Con-

figuration incorrect, Bad fan

status switch.

Supply Fan in Hand

sfan_hand_alarm

Ramp down Operations

Automatic

Bad Fan Status Switch, Configur-

ation incorrect.

Compressor Safety

comp_alarm

Alert Generated

Automatic

Compressor would not start

Space Temp Sensor

spt_fail

Ramp down Operations

Automatic

Faulty, shorted, or open thermis-

tor caused by wiring error or

loose connection.

Supply Air Temp

Sensor

sat_alarm

Economizer Disabled

Automatic

Faulty, shorted, or open thermis-

tor caused by wiring error or

loose connection.

Outdoor Air Temp

Sensor Alarm

oat_alarm

Economizer and Low ambient

DX cooling lockout disabled.

Automatic

Faulty, shorted, or open thermis-

tor caused by wiring error or

loose connection.

Space Relative

Humidity Sensor

sprh_alarm

Dehumidification disabled

Automatic

Sensor reading is out of range.

Bad sensor, bad wiring, or sensor

configured incorrectly.

IAQ Sensor

iaq_alarm

No IAQ Operation

Automatic

Sensor reading is out of range.

Bad sensor, bad wiring, or sensor

configured incorrectly.

OAQ Sensor

oaq_alarm

Set OAQ to 400

Automatic

Sensor reading is out of range.

Bad sensor, bad wiring, or sensor

configured incorrectly.

Space Temperature

spt_alrm_status

Alert Generated

Automatic

Space value is less then the low

allowed value or Space value is

greater then the high allowed

value

Alarming

Temperature

spt_alrm_temp

Shows temperature that

caused alarm

N/A

N/A

Alarm Limit

Exceeded

spt_alrm_lmt

Shows the limit that was ex-

ceeded

N/A

N/A

High Supply Air

Temperature

sat_hi_alarm

Alert Generated

Automatic

SAT is greater then the configura-

tion for more then 5 minutes

Low Supply Air

Temperature

sat_lo_alarm

Alert Generated

Automatic

SAT is less then the configuration

for more then 5 minutes

Setpoint Slider

slidepot_alarm

Set Offset to zero

Automatic

STO sensor is open for more then

5 seconds

Switch Configuration

di_cfg_alarm

Disable only wrong switch

functions

Configure correctly

More then one discrete input is

configured to provide the same

function.

Analog Input

Configuration

ai_cfg_alarm

Disable 4 selectable analog

inputs

Configure correctly

More then one analog input is

configured to provide the same

function.

High Space Relative

Humidity

sprh_hi_alarm

Alert Generated

Automatic

IRH is greater then the configura-

tion for more then 15 minutes

Low Space Relative

Humidity

sprh_lo_alarm

Alert Generated

Automatic

IRH is less then the configuration

for more then 5 minutes

High CO2

co2_alarm

Alert Generated

Automatic

CO2 reading is above the config-

uration for 1 minute

Supply Fan Runtime

sfan_rntm_alarm

Alert Generated

zero the timer

Supply fan run time exceeded

user defined limit

Compressor 1 Runtime

comp1_rntm_alar

m

Alert Generated

zero the timer

Compressor run time limit is ex-

ceeded

Compressor 2 Runtime

comp2_rntm_alar

m

Alert Generated

zero the timer

Compressor run time limit is ex-

ceeded

Filter

filter_alarm

Alert Generated

Automatic / reset

timer

Dirty Filter, supply fan run time ex-

ceeded, filter switch configuration

wrong.

Airside Linkage Alarm

air_linkage_fail

Alert Generated

Automatic

Linkage communication failed