APPENDIX A -- USER INTERFACE MENUS (CON’T)

Status Menus

BACview MENU

POINT NAME

BACnet OBJECT

RANGE

FIELD ASSISTANT

MENU

HOME

Select function below

Properties/Equipment

STATUS

STATUS

Status

System Mode

mode_status

1=Disabled

2=Test

3=Run

Operating Mode

run_status

1=Off

2=Fan Only

3=Economizer

4=Cooling

5=Heating

6=Dehumidification

7=Test

8=Shutdown

9=Unocc Free Cooling (NT-

FC)

Supply Fan Status

sfan_status

Off/Running

Space Temperature --- Prime Vari-

able

space_temp

xxx ° F

Supply Air Temperature

sa_temp

xxx ° F

Outdoor Air Temperature

oa_temp

xxx ° F

Space Relative Humidity

space_rh

0---100 %

Indoor Air CO2

iaq

0---5000 ppm

Outdoor Air CO2

oaq

0---5000 ppm

Economizer Output

econ_output

0---100 %open

LINKAGE

AIR LINKAGE

Linkage

Airside Linkage Status

a_link_status

Not Active/Active

Number of Providers

link_collector/4602

xx

Occupancy Status

link_occ

Unoccupied/Occupied

Space Temperature

link_spt

xxx ° F

Occupied Cooling Setpoint

link_occ_cl_stpt

55---80 ° F

Occupied Heating Setpoint

link_occ_ht_stpt

55---80 ° F

Unoccupied Cooling Setpoint

link_unocc_cl_stpt

75---130 ° F

Unoccupied Heating Setpoint

link_unocc_ht_stpt

55---85 ° F

Indoor Air CO2 (ppm)

link_iaq

xxxx ppm

Space Relative Humidity

link_sprh

xxx %