Input 5 -- This input is a discrete input and can be

configured to be one of six different functions: No

Function, Fire Shutdown, Fan Status, Filter Status,

Remote Occupancy, or Door Contact. This input can also

be configured to be either a Normally Open (N/O) or a

Normally Closed (N/C) switch. Input 5 is factory wired to

pin J1-10. Field accessories can be wired to its parallel

pin J5-3.

Software Default = Fire Shutdown and N/C

Factory Default = Fire Shutdown and N/O
Input 8 -- This input is a discrete input and can be

configured to be one of six different functions: No

Function, Enthalpy Switch, Fan Status, Filter Status,

Remote Occupancy, or Door Contact. This input can also

be configured to be either a Normally Open (N/O) or a

Normally Closed (N/C) switch. Input 8 is factory wired to

pin J2-6. Field accessories can be wired to its parallel pin

J5-1.

Software Default = Enthalpy Switch and N/O

Factory Default = No Function and N/O without factory

installed enthalpy sensor
Input 9 -- This input is a discrete input and can be

configured to be one of six different functions: No

Function, Humidistat, Fan Status, Filter Status, Remote

Occupancy, or Door Contact. This input can also be

configured to be either a Normally Open (N/O) or a

Normally Closed (N/C) switch. Input 9 is factory and

field wired to pin J5-7.

Factory Default = Humidistat and N/O
Space Sensor Type – This tells the controller what type

of space sensor is installed to run the unit. The three types

that can be used are: a standard 10k Type II thermistor

(T55), sensor with a setpoint offset slider bar (T56), or a

communicating sensor (SPT Sensor).

Range = T55, T56, or SPT Sensor

Default = T55

T5x Override Duration – Sets the override time duration

the unit will change from unoccupied to occupied when

the override button is pushed on the space sensor.

Range = 0-24 hours

Default = 1 hour

Service

Unit Type – This tells the control what type of unit it is

controlling. Heat/Cool refers to gas and electric heat

units. HP O/B Ctrl refers to a heat pump unit which

requires reversing valve control. HP Y1/W1 Ctrl refers to

a heat pump unit whose reversing valve is built in to the

cooling or heating call.

Factory Default = Heat/Cool for non-heat pump

units, or HP Y1/W1 Ctrl for heat pump units.

Compressor Stages – This refers to the number of

mechanical cooling stages available on a specific unit.

Set this point to “One Stage” if there is one compressor in

the specific unit, set to “Two Stage” if there are two

compressors in the unit, and set to “None” if economizer

cooling ONLY is desired.

Factory Default = “One Stage” for 1 compressor

units, or “Two Stages” for 2 compressor units

Economizer Exists – This tells the controller if there is an

economizer installed on the unit.

Factory Default = NO if no economizer, or YES if

there is an economizer installed

Reversing Valve Type – Sets the heat pump’s (HP O/B

Ctrl type) reversing valve function. O output type refers

to a valve that is energized for cooling, and B output type

refers to a valve that is energized for heating.

Default = O output type

Heat Type – Tells the controller which type of heat the

unit is capable of. Electric is any unit without gas and a

Gas unit is one which requires gas input for heating.

Factory Default = Electric for cooling only units

and heat pumps, or Gas for gas units.

Number of Heat Stages – Tells the controller how many

heat stages outputs are available for use.

See

configuration in Appendix A for details on specific unit

configuration.

Factory Default = 1 for single heat stage units,

2 for duel stage units, or 0 for cooling only units.

Continuous Occupied Exhaust – This point tells the

controller when to run the power exhaust if equipped on

the unit.

If set to YES, the power exhaust will be on all the time

when in occupied mode and will be off when in

unoccupied mode. If set to NO the power exhaust will be

controlled by the Power Exhaust Setpoint.

Default = NO

Indoor CO

2

Sensor Value @ Min mA – Sets the indoor

CO

2

value when the board reads 4 mA at input 1 or 2.

Default 0 ppm

Indoor CO

2

Sensor Value @ Max mA – Sets the indoor

CO

2

value when the board reads 20 mA at input 1 or 2.

Default 2000 ppm

Outdoor CO

2

Sensor Value @ Min mA – Sets the

outdoor CO

2

value when the board reads 4 mA at input 1

or 2.

Default 0 ppm

Outdoor CO

2

Sensor Value @ Max mA – Sets the

outdoor CO

2

value when the board reads 20 mA at input 1

or 2.

Default 2000 ppm

NOTE: The indoor and outdoor min and max mA setting

are used to set the linear curve of mA vs. PPM.

Clockset

This submenu screen allows you to set the date and time

manually. The Daylight Savings Time (DST) can also be

changed here. The date and time is automatically set

whenever software is downloaded. The clock is a 24 hour

clock and not am/pm. The time should be verified (and

maybe changed) according to unit location and time zone.

Factory Default = Eastern Standard Time