Sensors and accessories, User interfaces, Install analog sensors – Carrier 50HCQ04---12 User Manual

Page 4: Supply air sensor (sat), Outdoor air sensor (oat), Space temperature sensor (spt)

background image

4

Table 1 – RTU--OPEN Inputs and Outputs

POINT NAME

BACnet OBJECT

NAME

TYPE OF I/O

CONNECTION PIN

NUMBER(S)

DEDICATED INPUTS

Space Temp / Zone Temp

zone_temp

AI (10K Thermistor)

J20---1, 2

Supply Air Temperature

sa_temp

AI (10K Thermistor)

J2---1, 2

Outdoor Air Temperature

oa_temp

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

stpt_adj_offset

AI (100K Potentiometer)

J20---3

Safety Chain Feedback

safety_status

DI (24 VAC)

J1---9

Compressor Safety Status

comp_status

DI (24 VAC)

J1---2

Fire Shutdown Status

firedown_status

DI (24 VAC)

J1---10

Enthalpy Status

enthalpy_status

DI (24 VAC)

J2---6

Humidistat Input Status

humstat_status

DI (24 VAC)

J5---7

CONFIGURABLE INPUTS

Indoor Air CO2

iaq

AI (4---20 ma)

J4---2 or J4---5

Outdoor Air CO2

oaq

AI (4---20 ma)

Space Relative Humidity

space_rh

AI (4---20 ma)

Supply Fan Status*

sfan_status

DI (24 VAC)

J5---1 or J5---3 or

J5 5 or J5---7

Filter Status*

filter_status

DI (24 VAC)

Door Contact Input*

door_contact_status

DI (24 VAC)

Occupancy Contact*

occ_contact_status

DI (24 VAC)

OUTPUTS

Economizer Output

econ_output

AO (4---20ma)

J2---5

Supply Fan Relay State

sfan

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

DO Relay (24VAC , 1A)

J1---7

Heat Stage 1 Relay State

heat_1

DO Relay (24VAC , 1A)

J1---6

Heat Stage 2 Relay State

heat_2

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

pexh

DO Relay (24VAC , 1A)

J11---3

Dehumidification Relay State

dehum

DO Relay (24VAC, 1A)

J11---7, 8

* These inputs (if installed) take the place of the default input on the specific channel

Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for filed installation.

Refer to the input configuration and accessory sections for more detail.

Sensors and Accessories

The RTU-OPEN controller is configurable with the

following field-supplied sensors:
NOTE: Supply air temperature sensor (33ZCSENSAT) is
factory-installed.

S

Space temperature sensor (SPS, SPPL, SPP, SPPF,
33ZCT55SPT, 33ZCT56SPT, or 33ZCT59SPT

S

Indoor air quality sensor (33ZCSENCO2,
33ZCT55CO2, 33ZCT56CO2) required for demand
control ventilation.

S

Outdoor air quality sensor (33ZCTSENCO2)

S

CO

2

aspirator box (C33ZCCASPCO2) required for CO

2

return duct/outside air applications

S

Outdoor air enthalpy switch (33CSENTHSW)

S

Return air enthalpy sensor (33CSENTSEN) required for
differential enthalpy control

S

Space relative humidity sensor (33ZCSENSRH-01)

S

Duct relative humidity (33ZCSENDRH-01)

S

Humidistat (--HL--38MG-029)

S

Smoke Detectors (CRSMKSEN002A00,
CRSMKKIT002A00)

S

Fan and/or Filter Status (CRSTATUS001A00,
CRSTATUS005A00)

User Interfaces

S

BACview 6 Handheld (BV6H)

S

Virtual BACview (USB-L or USB-TKIT required)

S

Field Assistant (USB-TKIT required)

Install Analog Sensors

Supply Air Sensor (SAT)

The factory supplies the discharge (supply) air sensor with

the unit and is pre--wired. On 04-16 size units, the SAT is

secured to the unit’s supply duct opening. This sensor

must be relocated into the supply duct during unit

installation. On 17-30 size units, the SAT is mounted

through the side of the heat chamber below the fan deck,

and does NOT require relocation.

Outdoor Air Sensor (OAT)

The OAT is supplied with the economizer option or

accessory. It is wired through the 12-pin plug (PL6) in the

return air section of the unit and is mounted on the

economizer assembly.

Space Temperature Sensor (SPT)

There are 2 types of SPT sensors available from Carrier,

resistive input non-communicating (T55, T56, and T59)

and Rnet communicating (SPS, SPPL, SPP, and SPPF)

sensors. Each type has a variety of options consisting of:

timed override button, set point adjustment, a LCD

screen, and communication tie in. Space temperature can

be also be written to from a building network or zoning

system. However, it is still recommended that return air

duct sensor be installed to allow stand-alone operation for

back-up. Refer to the configuration section for details on

controller configurations associated with space sensors.