beautypg.com

Appendix a -- user interface menus (con’t), Standby bacview screen and login screen, System settings menu – Carrier 50HCQ04---12 User Manual

Page 28

background image

28

APPENDIX A -- USER INTERFACE MENUS (CON’T)

Standby BACview Screen and Login Screen

BACview MENU

POINT NAME

BACnet OBJECT

VALUE

STANDBY

RTU---OPEN

Operating Mode

run_status

1=Off

2=Fan Only

3=Economizer

4=Cooling

5=Heating

6=Dehumidification

7=Test

8=Shutdown

9=Unocc Free Cooling

(NTFC)

Space Temperature

space_temp

xxx ° F

Press any key to activate

HOME

Select function below

LOGIN/LOGOUT

Admin or User
Password

user: 0000 Admin:1111

System Settings Menu

BACview MENU

POINT NAME

BACnet OBJECT

RANGE

DEFAULT

HOME

Select function below

SYSTEM SETTINGS

SYSTEM SETTINGS

BACnet

BACnet Device Instance:

xxxxxxx

1610100

Base BACnet Device ID:

xxxxxxx

1610100

Autogenerate Device ID?

Y/N

Y

Keypad

Keypad Configuration

Inactivity Timeout:

1---255 minutes

10

BACnet Write Priority:

0---16

0

UserPw

View/Set User
Password:

xxxx

0000

Network

NETWORK

Max Masters

this_device/64

1---127

127

Max Info Frames

this_device/63

1---999

10

APDU Timeout (ms)

this_device/11

1---10000

3000

APDU Retries

this_device/73

1---10

3

MS/TP Baud Rate

this_device/4161(1)

9600---76800

76800

ClockSet

Set Current Time/Date (24 hr clock)

Time (hh:mm:ss):
Date (dd---mmm---yy):

DST

DST

Start Time:
Amount:
Entry #
Beg (mm---dd---yy)
End (mm---dd---yy)

TimeMstr

BACnet Time Master

Time Sync Mode

No Broadcast

Local Broadcast

Global Broadcast

No Broadcast

Time Sync Interval

1---9999 minutes

5