Appendix a -- user interface menus (con’t), Standby bacview screen and login screen, System settings menu – Carrier 50HCQ04---12 User Manual
Page 28
28
APPENDIX A -- USER INTERFACE MENUS (CON’T)
Standby BACview Screen and Login Screen
BACview MENU
POINT NAME
BACnet OBJECT
VALUE
STANDBY
RTU---OPEN
Operating Mode
run_status
1=Off
2=Fan Only
3=Economizer
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdown
9=Unocc Free Cooling
(NTFC)
Space Temperature
space_temp
xxx ° F
Press any key to activate
HOME
Select function below
LOGIN/LOGOUT
Admin or User
Password
user: 0000 Admin:1111
System Settings Menu
BACview MENU
POINT NAME
BACnet OBJECT
RANGE
DEFAULT
HOME
Select function below
SYSTEM SETTINGS
SYSTEM SETTINGS
BACnet
BACnet Device Instance:
xxxxxxx
1610100
Base BACnet Device ID:
xxxxxxx
1610100
Autogenerate Device ID?
Y/N
Y
Keypad
Keypad Configuration
Inactivity Timeout:
1---255 minutes
10
BACnet Write Priority:
0---16
0
UserPw
View/Set User
Password:
xxxx
0000
Network
NETWORK
Max Masters
this_device/64
1---127
127
Max Info Frames
this_device/63
1---999
10
APDU Timeout (ms)
this_device/11
1---10000
3000
APDU Retries
this_device/73
1---10
3
MS/TP Baud Rate
this_device/4161(1)
9600---76800
76800
ClockSet
Set Current Time/Date (24 hr clock)
Time (hh:mm:ss):
Date (dd---mmm---yy):
DST
DST
Start Time:
Amount:
Entry #
Beg (mm---dd---yy)
End (mm---dd---yy)
TimeMstr
BACnet Time Master
Time Sync Mode
No Broadcast
Local Broadcast
Global Broadcast
No Broadcast
Time Sync Interval
1---9999 minutes
5