beautypg.com

Sensor(s) (iaq and oaq) – Carrier 50HCQ04---12 User Manual

Page 6

background image

6

Resistive Non--Communicating Sensor Wiring
For sensor with setpoint adjustment up to 500 ft (152m),

use three-conductor shielded cable 20 gauge wire to

connect the sensor to the controller. For non set point

adjustment (slidebar) or return air duct sensor, an

unshielded, 18 or 20 gauge, two-conductor, twisted pair

cable may be used. Below is the list of the connections of

the SPT to the RTU-OPEN, refer to Fig. 3 and 4 for

typical connections at the sensor.

S

J20-1 = temperature sensor input (SEN)

S

J20-2 = sensor common

S

J20-3 = Setpoint adjustment input (SET)

NOTE:

See Fig. 5 for space temperature sensor

averaging. T55/56 Override button will no longer function
when sensors are averaged. Only Sensor 1 T56 STO input
can be used.

2

3

4

5

6

1

SW1

SEN

SET

Cool

Warm

BRN (GND)

BLU (SPT)

SENSOR WIRING

JUMPER
TERMINALS
AS SHOWN

BLK
(T56)

C07131

Fig. 3 -- Space Temperature Sensor

Typical Wiring (33ZCT56SPT)

OR

SET

SEN

OPB

COM- PWR+

BLU (SPT)

BLK (STO)

24 VAC

SENSOR

WIRING

POWER
WIRING

BRN (COM)

NOTE: Must use a separate isolated transformer.

Fig. 4 -- Space Temperature Sensor

Typical Wiring (33ZCT59SPT)

Rnet Communicating Sensor Wiring
The Rnet bus allows local communication with the

RTU-OPEN, including communicating sensors. The Rnet

bus can hold up to 6 devices in the following

combinations

wired

in

daisy-chain

or

hybrid

configuration:

S

1-4 SPS sensor(s)

S

1 SPPL, SPP, or SPPF sensor

S

1-4 SPS sensor(s), and 1 SPPL, SPP, or SPPF sensor

S

Any of the above combinations, plus up to 2
BACview

6

s

NOTE: Additional SPS sensors and BACview

6

must be

addressed. Use the jumpers on the SPS sensor’s circuit
board and refer to the BACview

6’

s installation instructions

for addressing.
For Rnet wiring up to 500ft (152m), use 18 AWG 4

conductor unshielded plenum rated cable.

The

RTU-OPEN’s J13-RNET connection has a 4 pin Phoenix

connector wired as described below, Fig. 6 shows sensor

Rnet wiring.

S

RNET -- 1 = Signal ground (GND)

S

RNET -- 2 = Signal (Rnet+)

S

RNET -- 3 = Signal (Rnet--)

S

RNET -- 4 = Power (+12v)

CO

2

Sensor(s) (IAQ and OAQ)

The indoor air quality (IAQ) and outdoor air quality

(OAQ) sensors monitor carbon dioxide (CO

2

) levels. This

information is used to monitor the quality of air in terms

of parts per million (PPM). The same sensor is used for

inside, outside, and duct monitoring, except an aspirator

box is required for outside and duct mounting. The CO

2

sensor is preset for a range of 0 to 2000 ppm and a linear

mA output of 4 to 20. The rooftop unit may have a factory

installed CO

2

sensor on the side of the economizer

assembly in the return air section of the unit and is

pre-wired and pre-configured at the factory. For field

installed sensors, a field supplied transformer must be

used to power the sensor.

Refer to the instructions

supplied with the CO

2

sensor for electrical requirements

and terminal locations. RTU-OPEN configurations must

be changed after adding a CO

2

sensor. See below and Fig.

7 for typical CO

2

sensor wiring.

S

J4--2 or J4--5 = 4--20mA signal input

S

J4--3 or J4--6 = signal common

NOTE: The factory used J4-2&3 for CO

2

(IAQ) sensor

inputs.
Combination Temperature and CO

2

Sensor

If using a combination temperature and CO

2

sensor

(33ZCT55CO2 or 33ZCT56CO2), refer to the installation

instructions provided with the sensor.

This manual is related to the following products: