RTU--OPEN START--UP SHEET

RTU Model Number:

Date:

RTU Serial Number:

Performed by:

RTU---OPEN Software Version:

Company:

Protocol and Boad Rate:

Network Address:

CONFIGURATION POINTS

BACview

MENU

POINT NAME

BACnet

OBJECT

RANGE

DEFAULT

ENTRY

HOME

Select function below

CONFIG

CONFIGURATION

SET-

POINT

SETPOINTS

Occupied Heating Setpoint

occ_ht_stpt

40---90 ° F

70

Occupied Cooling Setpoint

occ_cl_stpt

55---99 ° F

74

Unoccupied Heating Setpoint

unocc_ht_stpt

40---90 ° F

55

Unoccupied Cooling Setpoint

unocc_cl_stpt

55---99 ° F

90

Effective Cool Setpoint

eff_cl_stpt

xx ° F

Effective Heat Setpoint

eff_ht_stpt

xx ° F

Optimal Start

optm_start

0---4 hr

4

Occ Relative Humidity Setpoint

occ_dehum_stpt

0---unocc setpoint

%rh

60

Unocc Relative Humidity Setpoint

unocc_de-

hum_stpt

30---100 %rh

95

DCV Max Ctrl Setpoint

iaq_stpt_max

0---9999 ppm

650

Power Exhaust Setpoint

pexh_stpt

20---90 %Open

50

ALARMS

ALARM CONFIGURATION

SPACE TEMPERATURE ALARM

Occupied Alarm Hysteresis

occ_spt_alrm_hyst

2---20° F

3

Alarm Delay (min/deg)

spt_alrm_delay

0---30 minutes

10

Unoccupied Low SPT Alarm Limit

uno_spt_alrm_lo_l

mt

35---90 ° F

45

Unoccupied High SPT Alarm Limit

uno_spt_alrm_hi_l

mt

45---100 ° F

95

SUPPLY AIR TEMPERATURE ALARM

Low SAT Alarm Limit

sat_lo_alrm_lim

15---90 ° F

35

High SAT Alarm Limit

sat_hi_alrm_lim

90---175 ° F

160

SPACE HUMIDITY ALARM

Low Space Humidity Alarm Limit

sprh_lo_alrm_lim

0---99 %rh

30

High Space Humidity Alarm Limit

sprh_hi_alrm_lim

0---99 %rh

70

IAQ / VENTILATION ALARM

Occ High CO2 Alarm Limit (ppm)

iaq_occ_hi_lmt

0---9999 ppm

1200