Rtu--open start--up sheet, Configuration points – Carrier 50HCQ04---12 User Manual
Page 41
41
RTU--OPEN START--UP SHEET
RTU Model Number:
Date:
RTU Serial Number:
Performed by:
RTU---OPEN Software Version:
Company:
Protocol and Boad Rate:
Network Address:
CONFIGURATION POINTS
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE
DEFAULT
ENTRY
HOME
Select function below
CONFIG
CONFIGURATION
SET-
POINT
SETPOINTS
Occupied Heating Setpoint
occ_ht_stpt
40---90 ° F
70
Occupied Cooling Setpoint
occ_cl_stpt
55---99 ° F
74
Unoccupied Heating Setpoint
unocc_ht_stpt
40---90 ° F
55
Unoccupied Cooling Setpoint
unocc_cl_stpt
55---99 ° F
90
Effective Cool Setpoint
eff_cl_stpt
xx ° F
Effective Heat Setpoint
eff_ht_stpt
xx ° F
Optimal Start
optm_start
0---4 hr
4
Occ Relative Humidity Setpoint
occ_dehum_stpt
0---unocc setpoint
%rh
60
Unocc Relative Humidity Setpoint
unocc_de-
hum_stpt
30---100 %rh
95
DCV Max Ctrl Setpoint
iaq_stpt_max
0---9999 ppm
650
Power Exhaust Setpoint
pexh_stpt
20---90 %Open
50
ALARMS
ALARM CONFIGURATION
SPACE TEMPERATURE ALARM
Occupied Alarm Hysteresis
occ_spt_alrm_hyst
2---20° F
3
Alarm Delay (min/deg)
spt_alrm_delay
0---30 minutes
10
Unoccupied Low SPT Alarm Limit
uno_spt_alrm_lo_l
mt
35---90 ° F
45
Unoccupied High SPT Alarm Limit
uno_spt_alrm_hi_l
mt
45---100 ° F
95
SUPPLY AIR TEMPERATURE ALARM
Low SAT Alarm Limit
sat_lo_alrm_lim
15---90 ° F
35
High SAT Alarm Limit
sat_hi_alrm_lim
90---175 ° F
160
SPACE HUMIDITY ALARM
Low Space Humidity Alarm Limit
sprh_lo_alrm_lim
0---99 %rh
30
High Space Humidity Alarm Limit
sprh_hi_alrm_lim
0---99 %rh
70
IAQ / VENTILATION ALARM
Occ High CO2 Alarm Limit (ppm)
iaq_occ_hi_lmt
0---9999 ppm
1200