CONFIGURATION POINTS (CON’T)
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE
DEFAULT
ENTRY
HOME
Select function below
CONFIG
CONFIGURATION
UNIT
UNIT CONFIGURATION
Fan Mode
fan_mode
1=Auto
2=Continuous
3=Always On
Continuous
Unit Start Delay
start_delay
0---30 sec
5
Fan Off Delay
fan_delay_off
0---180 sec
90
Minimum Cooling SAT
sat_cl_min
45---75 ° F
50
Maximum Heating SAT
sat_ht_max
95---150° F
120
Vent Dmpr Pos / DCV Min Pos
econ_min
0---100 %Open
20
DCV Max Vent Damper Pos
iaq_dpr_max
10---60 %Open
50
S Fan Service Alarm Timer
sfan_service_hrs
0---9999 hr
0
Comp 1 Service Alarm Timer
comp1_ser-
vice_hrs
0---9999 hr
0
Comp 2 Service Alarm Timer
comp2_ser-
vice_hrs
0---9999 hr
0
Filter Service Alarm Timer
filter_service_hrs
0---9999 hr
600
Pushbutton Override
pb_enable
Disable/Enable
Enable
Setpoint Adjustment
stpt_adj_enable
Disable/Enable
Enable
Setpoint Adjustment Range
stpt_adj_range
+/--- 0---5 ° F
5
Cooling Lockout Temperature
oat_cl_lockout
0---80° F
45
Economizer High OAT Lockout Temp
oat_ec_lockout
55---80° F
75
HP Rev Cycle Lockout Temp
hp_rev_cycle_lock-
out
---20---30° F
---3
Heating Lockout Temperature
oat_ht_lockout
35---150° F
65
Unocc Free Cool Enable
ntfc_ena
Disable/Enable
Disable
Setpoint Separation
min_stpt_sep
2---10 ° F
5
Occupancy Source
occ_source
1=Always occupied
2=BACnet Sched-
ule
3=BAS On/Off
4=Remote Occ In-
put
Always Occupied
CAL-
IBRATE
SENSOR CALIBRATION
Space Temp Calibration
spt_offset
---9.9---10° F
0
Supply Air Temp Calibration
sat_offset
---9.9---10° F
0
Outdoor Air Temp Calibration
oat_offset
---9.9---10° F
0