2 i/o communication – KEYENCE DL-DN1 User Manual
Page 38

3-2 I/O Communication
3-8
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (GT2) -
3
Co
mm
u
ni
c
a
ting
w
ith t
he G
T
2
s
er
ie
s
Status details
Error information list
Name
Description
Reading range
Error status
An error occurred with the DL-DN1 or sensor amplifier, or the
DL-DN1 is not communicating properly with the sensor amplifier.
If an error exists, the error ID number and error code are stored.
0: No Error
1: Error
Sensor ready
The sensor amplifier has started and is ready.
0: Starting
1: Ready
Error ID number
The error ID number is stored in the range of bit 0 (LSB) to bit 4
(MSB).
Error code
The error code is stored in the range of bit 8 (LSB) to bit 12
(MSB).
Error ID
number
(HEX)
Error
code
(HEX)
Description
Cause
Corrective action
00h
01h
Initialization error
Error encountered during
initialization.
Check the number of
connected sensor amplifiers
and the connection to the
sensor amplifiers, and then
cycle power. If the error
remains, contact your nearest
sales office.
04h
Mixed connection error
A foreign sensor amplifier (i.e.,
one that is not compatible) is
connected.
Remove the foreign sensor
amplifier.
06h
Number-of-units error
More sensor amplifiers are
connected than are permitted.
Check the number of
connected sensor amplifiers.
nnh
(01h -
0Fh)
01h
Error 1 for sensor amplifier of
ID number nn
Overcurrent error (ErC)
Refer to the GT2 series user's
manual.
02h
Error 2 for sensor amplifier of
ID number nn
Head error (ErH)
03h
Error 3 for sensor amplifier of
ID number nn
EEPROM error (ErE)
04h
Error 4 for sensor amplifier of
ID number nn
Jam check error (Er.chK)
05h
Error 5 for sensor amplifier of
ID number nn
Self-timing delay error (Er.dLY)
06h
Error 6 for sensor amplifier of
ID number nn
Number-of-units error (Er.Unit)
07h
Error 7 for sensor amplifier of
ID number nn
Calculation error (Er.CAL)
08h
Error 8 for sensor amplifier of
ID number nn
Calculation-only mode error
(Er.noH)
1Dh
02h/
04-07h
System error
An error occurred in the internal
system.
Check the connection to the
sensor, and then cycle power. If
the error can not be corrected,
contact your nearest sales
office.
03h
Model error
There is a sensor amplifier
connected that is incompatible
with the DL-DN1.
Connect a sensor amplifier of a
compatible model.
1Fh
-
No error
-
-