beautypg.com

3 names and functions of each part, Names and functions of each part -5, Names and functions of each part – KEYENCE DL-DN1 User Manual

Page 15

background image

1-5

1

Bef

o

re

U
s

in

g

- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (GT2) -

1-3

Names and Functions of Each Part

This section describes the part names and functions of the DL-DN1.

Item

Description

(1) Address setting switch

Sets the DeviceNet node address of the DL-DN1.
x10

: Ten's digit

x1

: One's digit

Setting range: 00 to 63
Default value: 63
When setting the node address of the DL-DN1 from
the DeviceNet master unit, set it in the range of 64 to
99. The DL-DN1 is switched to PGM mode.

When the DL-DN1 is set in the PGM mode
and the power is turned on, the address
of the DL-DN1 is the same as used when
the DL-DN1was started last time.
When the DL-DN1 in the factory default
setting is set to the PGM mode, the node
address of the DL-DN1 is 63. Do not start
multiple DL-DN1 units in factory default
setting in the PGM mode, as that will
result in a network error because of the
duplicate node addresses.

(6) Sensor amplifier connector

(for DIN rail mounting type)

(8) DeviceNet connector

(2) Operating mode setting switch

(1) Address setting switch

(7) Sensor amplifier connector

(for panel mounting type
and large display type)

(4) Network status indicator (green/red)

(5) Sensor communication indicator (green/red)

(3) Module status indicator (green/red)

DL

-DN

1

20-30V DC, Class2

15JN

IND.CONT.EQ.

Point