To verify the correct execution of the calibration command:
• Write the sample weight value to the “Sample Weight for calibration” module;
• Write the value 0 to the “”Sample Weight for calibration” module;
• Send the command 101 “Sample weight storage for calibration” to the Command Register;
• The operation works correctly if the module value “Sample Weight for calibration” goes to zero.
Changing some instrument parameters via keyboard can take the Profibus network out of the data exchange
status and put the PLC in stop status; when programming the instrument the plant must be in stand-by status
3.8
SCT20-IP (EtherNet/IP)
The instrument works as a device in a Ethernet/IP network.
Load the included eds file (TLBEIP.eds) in the Ethernet/IP scanner’s development instrument. Or you can open
Class 1 I/O Connection with the following settings:
• Assembly Instance = 101; Size = 10
• Assembly Instance = 102; Size = 5
• Assembly Instance = 128; Size = 0
The data exchanged by SCT20-IP are:
Outgoing Data from SCT20-IP (Read)
Addresses
Internal Status [2 bytes]
0x0000-0x0001
Gross Weight [4 bytes]
0x0002-0x0005
Net Weight [4bytes]
0x0006-0x0009
Setpoint [4 bytes]
0x000A-0x000D
Status Register [2 bytes]
0x000E-0x000F
Digital Inputs Status [2 byte]
0x0010-0x0011
Digital Outputs Status [2 byte]
0x0012-0x0013
Input Data to SCT20-IP (Write)
Addresses
Write Enable [2 bytes]
0x0000-0x0001
Command Register [2 bytes]
0x0002-0x0003
Digital Outputs Command [2bytes]
0x0004-0x0005
Setpoint [4 bytes]
0x0006-0x0009
Note
EtherNet/IP