6 profibus settings – Rice Lake Signal Conditioning Transmitter/Indicators User Manual
Page 24

20 SCT Weight Transmitter Operator’s Manual
Analog Output Type Scale Corrections
Minimum and maximum values which can be set for the zero and full scale corrections Refer to COr 0 and COr FS.
The analog output may also be used in the opposite manner, i.e. the weight setting that corresponds to the
analog zero may be greater than the weight set for the analog full scale. The analog output will increase
towards full scale as the weight decreases; the analog output will decrease as the weight increases.
E.g.: analog output type having selected 0-10V
ANA 0 = 10000 ANA FS = 0
Weight = 0 kg
analog output = 10 V
Weight = 5000 kg
analog output = 5 V
Weight = 10000 kg
analog output = 0 V
2.6
Profibus Settings
1. Press and hold
and
to enter set-up menu. CALIb will be displayed.
2. Press
or
until PrOFI is displayed, press
.
3. Addr is displayed, press
.
4. Press
or
until desired value is displayed, press
.
5. Press
twice to exit set-up menu.
Analog Output Type
Minimum
Maximum
0–10 V
-0.15
10.2
0–5 V
-0.15
5.5
-10 +10 V
-10.3
10.2
-5 +5 V
-5.5
5.5
0-20 mA
-0.2
22
4-20 mA
-0.2
22
Parameter
Choices
Description
Addr
1
-99
1 *
Set instrument address in the Profibus network.
* - indicates default value.
Note
Profibus