Rice Lake Signal Conditioning Transmitter/Indicators User Manual
Page 27

Configuration 23
Front Panel Configuration
1. Press and hold
and
to enter set-up menu. CALIb will be displayed.
2. Press
or
until EtHnEt is displayed, press
.
3. Press
or
until desired parameter is displayed, press
.
4. Press
or
until desired value is displayed, press
.
5. Press
twice to exit set-up menu.
NodE
(Continued)
Hdr1 P
Continuous weight transmission protocol, streams net and gross including decimal. (see
Section 3.14) (set: BAUD=9600,PARITY=none, STOP=1)
Hdr1 PN
Continuous weight transmission protocol (see Section 3.14)
(set: BAUD=9600,PARITY=none, STOP=1)
When the remote display is set to gross weight:
- if the instrument displays the gross weight, the remote display shows the gross weight.
- if the instrument shows the net weight the remote display shows the net weight alternated
with the message “net”
bAud
2400
4800
9600 *
1
9200
38400
115200
Transmission speed.
The baud rate must be the same as the baud rate setting in the Serial
Communications Settings, see Section 2.9.
ADDR
1-99
1 *
Instruments address
HERTZ
Maximum Transmission Frequency
To be set when the CONTIN transmission protocol is selected. (see Figure 2-7)
1
0Hz *
20Hz
Max setting with min 2400 baud rate
30Hz
40Hz
Max setting with min 4800 baud rate
50Hz
60Hz
70Hz
80Hz
Max setting with min 9600 baud rate
100Hz
Max setting with min 19200 baud rate
200Hz
Max setting with min 38400 baud rate
300Hz
Max setting with min 38400 baud rate
dELAY
0-200 msec
0 *
Delay in milliseconds which elapses before the instrument replies
PAritY
nOnE *
EUEn
Odd
parity none
even parity
odd parity
StOP
1 *
2
Stop bit
* - indicates default value.
** - These settings do not function with Firmware 1.02.00 or lower.
Parameter
Choices
Description
Note