34 SCT Weight Transmitter Operator’s Manual
3.5
Alarms
DeviceNet Error (DeviceNet Models Only): A problem in the DeviceNet communication is marked by a lack of
flashing or a slow flashing (duration about 0.5 s) of the DeviceNet status LED.
Profibus Error (Profibus Models Only): A problem in the Profibus communication is marked by a lack of
flashing or a slow flashing (duration about 0.5 s) of the Profibus status LED.
Ethernet Error (Ethernet Models Only): A problem in the Ethernet communication is marked by a slow
flashing (duration about 0.5 s) of the Ethernet status LED.
Modbus/TCP Error (Modbus/TCP Models Only): A problem in the Modbus/TCP communication is marked by
a slow flashing (duration about 0.5 s) of the Modbus/TCP status LED.
* For RIP remote displays, if the message exceeds 5 digits the display reads
------
.
In case of alarm the relays, not managed by Modbus, Modbus/TCP or DeviceNet, open.
In Analog Models only, if an alarm becomes active the relays open and the analog outputs go to the lowest
possible value according to the following table:
Display
Description
ErCEL
Load cell is not connected or is incorrectly connected; the load cell signal exceeds 39 mV; the conversion electronics
(A/D converter) is malfunctioning; the load cell is a 4-wire and there are no jumpers between EX- and REF- and
between EX+ and REF+.
Er OL
Weight display exceeds 110% of the full scale.
Er Ad
Internal instrument converter failure; check load cell connections, if necessary contact Technical Assistance.
---------
The weight exceeds the maximum weight by 9 divisions.
Er OF
Maximum displayable value exceeded (value higher than 999999 or lower than -999999).
t
------
Weight too high: zero setting not possible.
NAH-PU
This message appears in the test weight setting, in Weight (Span) Calibration, after the fifth test weight value has
been entered.
Err0r
The value set for the parameter is beyond the permitted values; press
to quit the setting mode leaving the
previous value unchanged.
Example: a number of decimals is selected for full scale which exceeds the instrument's display potential;
value above the maximum setting value; the weight value set in test weight verification does not match the
detected mV increase.
bLOC
Lock is active on menu item, keypad or display.
nOdl SP
It’s not possible to display the number properly because it is greater than 999999 or less than -999999.
Table 3-1. Alarm Descriptions
MODE
ErCEL
Er OL
Er Ad
---------
Er OF
t-----
Bit LSB
76543210
xxxxxxx1
76543210
xxxx1xxx
76543210
xxxxxx1x
76543210
xxxxx1xx
76543210 On
gross:
xxx1xxxx On
net: xx1xxxxx
The response to the zero
command is a 'value not
valid' error (error code 3)
Status Register
MODBUS RTU
ASCII
__O-F_ __O-L_ __O-F_ __O-L_ __O-F_ &aa#CR
RIP *
__O-F_ __O-L_ __O-F_ __O-L_ __O-F_ __O-F_
HDRIP-N
_ERCEL _ER_OL _ER_AD ###### _ER_OF O__SET
CONTIN
_ERCEL _ER_OL _ER_AD ^^^^^^ _ER_OF O__SET
Table 3-2. Serial Protocols Alarms
Range
0/20mA
4/20 mA
0/5 V
0/10 V
-10/10 V
-5/5 V
Output
Value
-0.2 mA
3.5 mA
-0.5 V
-0.5 V
0 V
0 V
Note