Appendix b — ccn tables (cont) – Carrier AQUASNAP MPW015-045 User Manual

Page 71

background image

71

APPENDIX B — CCN TABLES (cont)

CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)

CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings)

CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP)

CCN CONFIGURATION TABLES — HPA

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

COOLING RESET
Cooling Reset Type

N

0

CRST_TYP

4-20 MA RESET
4-20 - Degrees Reset

NNN.n

deltaF

420_DEG

REMOTE RESET
Remote - No Reset Temp

NNN.n

degF

REM_NO

Remote - Full Reset Temp

NNN.n

degF

REM_FULL

Remote - Degrees Reset

NNN.n

deltaF

REM_DEG

RETURN TEMPERATURE RESET
Return - No Reset Temp

NNN.n

deltaF

RTN_NO

Return - Full Reset Temp

NNN.n

deltaF

RTN_FULL

Return - Degrees Reset

NNN.n

deltaF

RTN_DEG

DEMAND LIMIT
Demand Limit Select

N

DMD_CTRL

Demand Limit at 20 mA

NNN

%

DMT20MA

Loadshed Group Number

NN

SHED_NUM

Loadshed Demand Delta

NN

%

SHED_DEL

Maximum Loadshed Time

NNN

mins

SHED_TIM

Demand Limit Switch 1

NNN

%

DLSWSP1

Demand Limit Switch 2

NNN

%

DLSWSP2

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

LEAD/LAG
Lead/Lag Chiller Enable

Dsable/Enable

LL_ENA

Master/Slave Select

Master/Slave

MS_SEL

Slave Address

NNN

SLV_ADDR

Lead/Lag Balance Select

N

LL_BAL

Lead/Lag Balance Delta

NNN

hours

LL_BAL_D

Lag Start Delay

NN

mins

LL_DELAY

Parallel Configuration

No/Yes

PARALLEL

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Service Password

NNNN

PASSWORD

Password Enable

Dsable/Enable

PASS_EBL

Metric Display

Off/On

DISPUNIT

Language Selection

N

LANGUAGE

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

SCT Delta for Comp A1

NNN.n

deltaF

A1SCTDT

SCT Delta for Comp A2

NNN.n

deltaF

A2SCTDT