Appendix b — ccn tables (cont) – Carrier AQUASNAP MPW015-045 User Manual
Page 71

71
APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)
CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings)
CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP)
CCN CONFIGURATION TABLES — HPA
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
COOLING RESET
Cooling Reset Type
N
0
CRST_TYP
4-20 MA RESET
4-20 - Degrees Reset
NNN.n
deltaF
420_DEG
REMOTE RESET
Remote - No Reset Temp
NNN.n
degF
REM_NO
Remote - Full Reset Temp
NNN.n
degF
REM_FULL
Remote - Degrees Reset
NNN.n
deltaF
REM_DEG
RETURN TEMPERATURE RESET
Return - No Reset Temp
NNN.n
deltaF
RTN_NO
Return - Full Reset Temp
NNN.n
deltaF
RTN_FULL
Return - Degrees Reset
NNN.n
deltaF
RTN_DEG
DEMAND LIMIT
Demand Limit Select
N
DMD_CTRL
Demand Limit at 20 mA
NNN
%
DMT20MA
Loadshed Group Number
NN
SHED_NUM
Loadshed Demand Delta
NN
%
SHED_DEL
Maximum Loadshed Time
NNN
mins
SHED_TIM
Demand Limit Switch 1
NNN
%
DLSWSP1
Demand Limit Switch 2
NNN
%
DLSWSP2
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
LEAD/LAG
Lead/Lag Chiller Enable
Dsable/Enable
LL_ENA
Master/Slave Select
Master/Slave
MS_SEL
Slave Address
NNN
SLV_ADDR
Lead/Lag Balance Select
N
LL_BAL
Lead/Lag Balance Delta
NNN
hours
LL_BAL_D
Lag Start Delay
NN
mins
LL_DELAY
Parallel Configuration
No/Yes
PARALLEL
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Service Password
NNNN
PASSWORD
Password Enable
Dsable/Enable
PASS_EBL
Metric Display
Off/On
DISPUNIT
Language Selection
N
LANGUAGE
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
SCT Delta for Comp A1
NNN.n
deltaF
A1SCTDT
SCT Delta for Comp A2
NNN.n
deltaF
A2SCTDT