Table 23 — Menu Configuration of 4 to 20 mA Cooling Set Point Control

Table 24 — 4 to 20 mA Reset

NOTE: The example above shows how to configure the chiller for
4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F
reset will occur at 20.0 mA. An EMM (energy management module)
is required.

To use outdoor air or space temperature reset, four variables

must be configured. In the Configuration mode under the sub-

mode RSET, items (Configuration

RSET

CRST),

(Configuration

RSET

RM.NO), (Configuration

RSET

RM.F), and (Configuration

RSET

RT.DG)

must be properly set. See Table 25 — Configuring Outdoor Air

and Space Temperature Reset. The outdoor air reset example

provides 0° F (0° C) chilled water set point reset at 85.0 F

(29.4 C) outdoor-air temperature and 15.0 F (8.3 C) reset at

55.0 F (12.8 C) outdoor-air temperature. The space tempera-

ture reset example provides 0° F (0° C) chilled water set point

reset at 72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) re-

set at 68.0 F (20.0 C) space temperature. The variable CRST

should be configured for the type of reset desired. The variable

RM.NO should be set to the temperature that no reset should

occur. The variable RM.F should be set to the temperature that

maximum reset is to occur. The variable RM.DG should be set

to the maximum amount of reset desired. Figures 15 and 16 are

examples of outdoor air and space temperature resets.

To use return reset, four variables must be configured. In the

Configuration mode under the sub-mode RSET, items CRST,

RT.NO, RT.F and RT.DG must be properly set. See Table 26

— Configuring Return Temperature Reset. This example pro-

vides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C)

cooler

T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler T. The

variable RT.NO should be set to the cooler temperature differ-

ence (

T) where no chilled water temperature reset should oc-

cur. The variable RT.F should be set to the cooler temperature

difference where the maximum chilled water temperature reset

should occur. The variable RM.DG should be set to the maxi-

mum amount of reset desired.

To verify that reset is functioning correctly proceed to Run

Status mode, sub-mode VIEW, and subtract the active set point

(Run Status

VIEW

SETP) from the control point (Run

Status

VIEW

CTPT) to determine the degrees reset.

MODE

(RED LED)

KEYPAD

ENTRY

SUB-MODE

KEYPAD

ENTRY

ITEM DISPLAY

ITEM

EXPANSION

COMMENT

CONFIGURATION

DISP

UNIT

OPT1

OPT2

CCN

RSET

SLCT

CLSP

0

COOLING SETPOINT SELECT

0

Scrolling Stops

0

Flashing ‘0’

3

Select ‘3’

3

Change Accepted

SUB-MODE

KEYPAD

ENTRY

ITEM DISPLAY

ITEM

EXPANSION

COMMENT

RSET

CRST

1

COOLING RESET

TYPE

0 = no reset
1 = 4 to 20 mA input
2 = Outdoor air temp
3 = Return Fluid
4 = Space Temperature

MA.DG

5.0 F

(2.8 C)

DEGREES COOL

RESET

Default: 0° F (0° C) Reset at 20 mA
Range: –30 to 30 F (–16.7 to 16.7 C)

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

IMPORTANT: Care should be taken when interfacing with

other control systems due to possible power supply differ-

ences: full wave bridge versus half wave rectification. Con-

nection of control devices with different power supplies

may result in permanent damage. ComfortLink™ controls

incorporate power supplies with half wave rectification. A

signal isolation device should be utilized if the signal gen-

erator incorporates a full wave bridge rectifier.