APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — UNIT (Unit Configuration)
CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)
CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)
CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Unit Type
N
UNIT_TYP
Unit Size
NNN
tons
SIZE
Compressor A1 Size
NNN
tons
SIZE_A1
Compressor A2 Size
NNN
tons
SIZE_A2
Compressor A3 Size
NNN
tons
SIZE_A3
Suction Superheat Setpt
NN.n
deltaF
SH_SP
Compressor A1 Digital?
No/Yes
CPA1TYPE
Maximum A1 Unload Time
NN
secs
MAXULTME
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Cooler Fluid
N
FLUIDTYP
Minimum Load Vlv Select
No/Yes
MLV_FLG
Return Gas Sensor Enable
Dsable/Enable
RGT_ENA
Enable OAT Sensor
Dsable/Enable
OAT_ENA
Dischrge Gas Temp Enable
Dsable/Enable
DISGASEN
CSB Boards Enable
Dsable/Enable
CSB_ENA
Reverse Rotation Enable
Dsable/Enable
REVR_ENA
Cooler Pump Control
Off/On
CPC
Cooler Pump Shutdown Dly
NN
mins
PUMP_DLY
EMM Module Installed
No/Yes
EMM_BRD
Enable Condenser Pump
N
CONDPMPE
Enable Cond Wtr Sensors
Dsable/Enable
CONDWTRS
Enable Cond Flow Switch
Dsable/Enable
CONDFLSW
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Control Method
N
CONTROL
Loading Sequence Select
N
SEQ_TYPE
Lead/Lag Circuit Select
N
LEAD_TYP
Cooling Setpoint Select
N
CLSP_TYP
Ramp Load Select
Dsable/Enable
RAMP_EBL
High LCW Alert Limit
NN.n
deltaF
LCW_LMT
Minutes off time
NN
mins
DELAY
Deadband Multiplier
N.n
Z_GAIN
Ice Mode Enable
Dsable/Enable
ICE_CNFG
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Schedule Number
NN
1
SCHEDNUM
Override Time Limit
N
0
hours
OTL
Timed Override Hours
N
0
hours
OVR_EXT
Timed Override
No/Yes
No
TIMEOVER