To manually reset ASTP, the compressor should be stopped

and allowed to cool. If the compressor is not stopped, the motor

will run until the motor protector trips, which occurs up to

90 minutes later. Advanced scroll temperature protection will

reset automatically before the motor protector resets, which

may take up to 2 hours.
High Discharge Gas Temperature Protection — Units

equipped with optional digital compressors have an additional

thermistor located on the discharge line, If discharge tempera-

ture exceeds 265 F (129.4 C), the digital compressor will be

shut off.

Alarms will also occur if the current sensor board malfunc-

tions or is not properly connected to its assigned digital input. If

the compressor is commanded OFF and the current sensor

reads ON, an alert is generated. This will indicate that a com-

pressor contactor has failed closed. In this case, a special mode,

Compressor Stuck on Control, will be enabled and all other

compressors will be turned off. An alarm will then be enabled

to indicate that service is required. Outdoor fans will continue

to operate. The condenser output is turned on immediately.

Alarms and Alerts —

These are warnings of abnormal

or fault conditions, and may cause either one circuit or the

whole unit to shut down. They are assigned code numbers as

described in Table 38.

Automatic alarms will reset without operator intervention if

the condition corrects itself. The following method must be

used to reset manual alarms:

Before resetting any alarm, first determine the cause of the

alarm and correct it. Enter the Alarms mode indicated by the
LED on the side of the scrolling marquee display. Press

and

until the sub-menu item RCRN “RESET

ALL CURRENT ALARMS” is displayed. Press

.

The control will prompt the user for a password, by displaying
PASS and WORD. Press

to display the default pass-

word, 1111. Press

for each character. If the password

has been changed, use the arrow keys to change each individu-
al character. Toggle the display to “YES” and press

.

The alarms will be reset.

Fig. 25 — Advanced Scroll Temperature

Protection Label

ENTER

ENTER

ENTER

ENTER

ENTER

Fig. 26 — Recommended Minimum Cool Down Time After Compressor is Stopped*

0

10

20

30

40

50

60

70

80

90

100

110

120

0

10

20

30

40

50

60

70

80

90

Compressor Unloaded Run Time (Minutes)

R

e

c

o

m

m

e

nde

d C

ool

ing

Ti

m

e

(Mi

nu

tes

)

*Times are approximate.
NOTE: Various factors, including high humidity, high ambient temperature,
and the presence of a sound blanket will increase cool-down times.