Ramp Loading — Ramp loading (Configura-

tion

SLCT

CRMP) limits the rate of change of leaving

fluid temperature. If the unit is in a Cooling mode and config-

ured for Ramp Loading, the control makes 2 comparisons be-

fore deciding to change stages of capacity. The control calcu-

lates a temperature difference between the control point and

leaving fluid temperature. If the difference is greater than 4° F

(2.2° C) and the rate of change (°F or °C per minute) is more

than the configured Cooling Ramp Loading value (CRMP),

the control does not allow any changes to the current stage of

capacity.
Low Entering Fluid Temperature Unloading — When the

entering fluid temperature is below the control point, the

control will attempt to remove 25% of the current stages being

used. If exactly 25% cannot be removed, the control removes

an amount greater than 25% but no more than necessary. The

lowest stage will not be removed.
Hot Gas Bypass — If equipped, the hot gas bypass valve is

energized only when one compressor is running on circuit A. If

the close control feature is enabled the hot gas bypass valve

may be used as needed to obtain leaving fluid temperature

close to set point.
Cooler Freeze Protection — The control will try to prevent

shutting the chiller down on a Cooler Freeze Protection alarm

by removing stages of capacity. If the cooler fluid selected

is Water, the freeze point is 34 F (1.1 C). If the cooler fluid

selected is Brine, the freeze point is the Brine Freeze Point (Set

Points

FRZ

BR.FZ). This alarm condition (A207) only

references leaving fluid temperature and NOT Brine Freeze

point. If the cooler leaving fluid temperature is less than the

freeze point plus 2.0° F (1.1° C), the control will immediately

remove one stage of capacity. This can be repeated once every

30 seconds.
Low Saturated Suction Protection — The control will try to

prevent shutting a circuit down due to low saturated suction

conditions by removing stages of capacity. The circuit alert

condition (T116) compares saturated suction temperature to the

configured Brine Freeze Point (Set Points

FRZ

BR.FZ).

The Brine Freeze point is a user-configurable value that must

be left at 34 F (1.1 C) for 100% water systems. A lower value

47

46

45

44

43

42

41

0

200

400

600

800

1000

TIME (SECONDS)

2 STARTS

3 STARTS

DEADBAND EXAMPLE

LW

T

(F)

MODIFIED
DEADBAND

STANDARD
DEADBAND

8

7

6

5

LW

T

(C)

LEGEND

LWT — Leaving Water Temperature

Fig. 11 — Deadband Multiplier

160

170

130

140

150

160

110

120

130

80

90

100

50

60

70

30

40

-30

-20

-10

0

10

20

30

40

50

60

70

80

S

CT (F)

SST (F)

LEGEND

Fig. 12 — Operating Envelope for R-410A Compressor

SCT

Saturated Condensing Temperature

SST

Saturated Suction Temperature

a30-4969