APPENDIX B — CCN TABLES (cont)
CCN DISPLAY TABLES — OPTIONS (Unit Parameters)
CCN MAINTENANCE TABLES — STRTHOUR
DESCRIPTION
VALUE
UNITS
POINT NAME
FORCIBLE
UNIT ANALOG VALUES
Cooler Entering Fluid
NNN.n
degF
COOL_EWT
N
Cooler Leaving Fluid
NNN.n
degF
COOL_LWT
N
Condenser Entering Fluid
NNN.n
degF
COND_EWT
N
Condenser Leaving Fluid
NNN.n
degF
COND_LWT
N
Lead/Lag Leaving Fluid
NNN.n
degF
DUAL_LWT
N
TEMPERATURE RESET
4-20 ma Reset Signal
NN.n
milliAmps
RST_MA
N
Outside Air Temperature
NNN.n
degF
OAT
Y
Space Temperature
NNN.n
degF
SPT
Y
DEMAND LIMIT
4-20 ma Demand Signal
NN.n
milliAmps
LMT_MA
N
Demand Limit Switch 1
Off/On
DMD_SW1
N
Demand Limit Switch 2
Off/On
DMD_SW2
N
CCN Loadshed Signal
N
DL_STAT
N
MISCELLANEOUS
Dual Setpoint Switch
Off/On
DUAL_IN
N
Cooler LWT Setpoint
NNN.n
degF
LWT_SP
N
Ice Done
Off/On
ICE_DONE
N
DESCRIPTION
VALUE
UNITS
POINT NAME
Machine Operating Hours
NNNNNN
hours
HR_MACH
Machine Starts
NNNNNN
CY_MACH
Compressor A1 Run Hours
NNNNNN.n
hours
HR_A1
Compressor A2 Run Hours
NNNNNN.n
hours
HR_A2
Compressor A3 Run Hours
NNNNNN.n
hours
HR_A3
Compressor A1 Starts
NNNNNN
CY_A1
Compressor A2 Starts
NNNNNN
CY_A2
Compressor A3 Starts
NNNNNN
CY_A3
PUMP HOURS
Cooler Pump Run Hours
NNNNNN.n
hours
HR_CPUMP
Condenser Pump Run Hours
NNNNNN.n
hours
HR_DPUMP