APPENDIX B — CCN TABLES (cont)

CCN DISPLAY TABLES — OPTIONS (Unit Parameters)

CCN MAINTENANCE TABLES — STRTHOUR

DESCRIPTION

VALUE

UNITS

POINT NAME

FORCIBLE

UNIT ANALOG VALUES
Cooler Entering Fluid

NNN.n

degF

COOL_EWT

N

Cooler Leaving Fluid

NNN.n

degF

COOL_LWT

N

Condenser Entering Fluid

NNN.n

degF

COND_EWT

N

Condenser Leaving Fluid

NNN.n

degF

COND_LWT

N

Lead/Lag Leaving Fluid

NNN.n

degF

DUAL_LWT

N

TEMPERATURE RESET
4-20 ma Reset Signal

NN.n

milliAmps

RST_MA

N

Outside Air Temperature

NNN.n

degF

OAT

Y

Space Temperature

NNN.n

degF

SPT

Y

DEMAND LIMIT
4-20 ma Demand Signal

NN.n

milliAmps

LMT_MA

N

Demand Limit Switch 1

Off/On

DMD_SW1

N

Demand Limit Switch 2

Off/On

DMD_SW2

N

CCN Loadshed Signal

N

DL_STAT

N

MISCELLANEOUS
Dual Setpoint Switch

Off/On

DUAL_IN

N

Cooler LWT Setpoint

NNN.n

degF

LWT_SP

N

Ice Done

Off/On

ICE_DONE

N

DESCRIPTION

VALUE

UNITS

POINT NAME

Machine Operating Hours

NNNNNN

hours

HR_MACH

Machine Starts

NNNNNN

CY_MACH

Compressor A1 Run Hours

NNNNNN.n

hours

HR_A1

Compressor A2 Run Hours

NNNNNN.n

hours

HR_A2

Compressor A3 Run Hours

NNNNNN.n

hours

HR_A3

Compressor A1 Starts

NNNNNN

CY_A1

Compressor A2 Starts

NNNNNN

CY_A2

Compressor A3 Starts

NNNNNN

CY_A3

PUMP HOURS
Cooler Pump Run Hours

NNNNNN.n

hours

HR_CPUMP

Condenser Pump Run Hours

NNNNNN.n

hours

HR_DPUMP