48 table 38 — alarm and alert codes (cont) – Carrier AQUASNAP MPW015-045 User Manual

Page 48

background image

48

Table 38 — Alarm and Alert Codes (cont)

See legend on page 51.

ALARM/

ALERT

CODE

ALARM

OR

ALERT

DESCRIPTION

WHY WAS THIS

ALARM

GENERATED?

ACTION TAKEN

BY CONTROL

RESET

METHOD

PROBABLE

CAUSE

A116

Alarm

Circuit A Low Cooler
Suction Temperature

Mode 7 caused the com-
pressor to unload 6 consecu-
tive times with less than a
30-minute interval between
each circuit shutdown.

Circuit shut down

Manual

Faulty expansion valve, low
refrigerant charge, plugged
filter drier, faulty suction
pressure transducer, low
cooler fluid flow

A122

Alarm

High Pressure Switch

Trip Circuit A

High Pressure A Switch

Input opento MBB

Circuit shut down

Manual

Faulty transducer/high
pressure switch.

A126

Alarm

Circuit A High
Discharge Pressure

SCT >Maximum condensing
temperature from operating
envelope

Circuit shut down

Automatic, only
after first 3 daily
occurrences.
Manual reset
thereafter. Read-
ing from OAT sen-
sor must drop 5 F
(2.8 C) before
restart

Faulty transducer/high
pressure switch, low/
restricted condenser
airflow

T133

Alert

Circuit A Low Suction
Pressure

Suction pressure below
34 psig for 8 seconds or
below 23 psig

Circuit shut down

Automatic
restart after first
daily occurrence.
Manual restart
thereafter.

Faulty or plugged EXV, low
refrigerant charge, EXV out
of adjustment, liquid
line valve partially closed

A140

Alert

Reverse Rotation
Detected

Incoming chiller power leads
not phased correctly

Chiller not allowed to
start.

Manual

Reverse any two incoming
power leads to correct. Check
for correct fan rotation first.

A150

Alarm

Emergency Stop

CCN emergency stop
command received

Chiller shutdown
without going through
pumpdown.

Automatic once
CCN command for
EMSTOP returns to
normal

CCN Network
command.

A151

Alarm

Illegal Configuration

One or more illegal
configurations exists.

Chiller is not allowed to
start.

Manual once
configuration errors
are corrected

Configuration error.
Check unit settings.

A152

Alarm

Unit Down Due to
Failure

Both circuits are down due
to alarms/alerts.

Chiller is unable
to run.

Automatic once
alarms/alerts are
cleared that pre-
vent the chiller from
starting.

Alarm notifies user
that chiller is 100%
down.

T153

Alert

Real Time Clock
Hardware Failure

Internal clock on MBB fails

Occupancy schedule
will not be used. Chiller
defaults to Local On
mode.

Automatic when
correct clock con-
trol restarts.

Time/Date/Month/
Day/Year not
properly set.

A154

Alarm

Serial EEPROM
Hardware Failure

Hardware failure with MBB

Chiller is unable
to run.

Manual

Main Base Board
failure.

T155

Alert

Serial EEPROM
Storage Failure

Configuration/storage
failure with MBB

No Action

Manual

Potential failure of
MBB. Download
current operating
software. Replace
MBB if error occurs again.

A156

Alarm

Critical Serial EEPROM
Storage Failure

Configuration/storage
failure with MBB

Chiller is not allowed
to run.

Manual

Main Base Board
failure.

A157

Alarm

A/D Hardware Failure

Hardware failure with
peripheral device

Chiller is not allowed
to run.

Manual

Main Base Board
failure.

T173

Alert

Loss of Communication
with EMM

MBB loses communication
with EMM

4 to 20 mA
temperature reset
disabled. Demand
Limit set to 100%. 4 to
20 mA set point
disabled.

Automatic

Wiring error, faulty
wiring or failed
Energy Management Module
(EMM).

T174

Alert

4 to 20 mA Cooling Set
Point Input Failure

If configured with EMM and
input less than 2 mA or
greater than 22 mA

Set point function
disabled. Chiller
controls to CSP1.

Automatic

Faulty signal
generator, wiring
error, or faulty EMM.

T176

Alert

4 to 20 mA
Temperature Reset
Input Failure

If configured with EMM
and input less than 2 mA or
greater than 22 mA

Reset function
disabled. Chiller
returns to normal set
point control.

Automatic

Faulty signal
generator, wiring
error, or faulty EMM.

T177

Alert

4 to 20 mA Demand
Limit Input Failure

If configured with EMM and
input less than 2 mA or
greater than 22 mA

Demand limit function
disabled. Chiller
returns to 100%
demand limit
control.

Automatic

Faulty signal
generator, wiring
error, or faulty EMM.