beautypg.com

Carrier AQUASNAP MPW015-045 User Manual

Page 14

background image

14

CONTROLS

General —

The 30MP liquid scroll chillers contain the

ComfortLink™ electronic control system that controls and

monitors all operations of the chiller.

The control system is composed of several components as

listed in the sections below. See Fig. 3 for a typical control box

drawing. See Fig. 4 and 5 for control schematics.

Main Base Board (MBB) —

See Fig. 6. The MBB is

the heart of the ComfortLink control system. It contains the

major portion of operating software and controls the operation

of the machine. The MBB continuously monitors input/output

channel information received from its inputs and from all other

modules. The MBB receives inputs from the discharge and

suction pressure transducers and thermistors. See Table 15. The

MBB also receives the feedback inputs from each compressor

current sensor board and other status switches. See Table 16.

The MBB also controls several outputs. Relay outputs con-

trolled by the MBB are shown in Table 17. Information is

transmitted between modules via a 3-wire communication bus

or LEN (Local Equipment Network). The CCN (Carrier Com-

fort Network) bus is also supported. Connections to both LEN

and CCN buses are made at the LVT (low voltage terminal).

Energy Management Module (EMM) —

The EMM

module is available as a factory-installed option or as a field-

installed accessory. The EMM module receives 4 to 20 mA

inputs for the leaving fluid temperature reset, cooling set point

and demand limit functions. The EMM module also receives

the switch inputs for the field-installed 2-stage demand limit

and ice done functions. The EMM module communicates the

status of all inputs with the MBB, and the MBB adjusts the

control point, capacity limit, and other functions according to

the inputs received.

Current Sensor Board (CSB) —

The CSB is used to

monitor the status of the compressors by measuring current and

providing an analog input to the main base board (MBB).

Enable/Off/Remote Contact Switch —

The Enable/

Off/Remote Contact switch is a 3-position switch used to

control the chiller. When switched to the Enable position the

chiller is under its own control. Move the switch to the Off

position to shut the chiller down. Move the switch to the

Remote Contact position and a field-installed dry contact can

be used to start the chiller. The contacts must be capable of

handling a 24 vac, 50-mA load. In the Enable and Remote

Contact (dry contacts closed) positions, the chiller is allowed to

operate and respond to the scheduling configuration, CCN

configuration and set point data. See Fig. 7.

Emergency On/Off Switch —

The Emergency On/Off

switch should only be used when it is required to shut the

chiller off immediately. Power to the MBB, EMM, and

marquee display is interrupted when this switch is off and all

outputs from these modules will be turned off. See Fig. 7.

Board Addresses —

The main base board (MBB) has a

3-position instance jumper that must be set to ‘1.’ The EMM

board has 4-position DIP switches. All switches are set to ‘On’

for all boards except the AUX2 board. The AUX2 board DIP

switch settings are shown on the wiring schematic.

Control Module Communication

RED LED — Proper operation of the control boards can be

visually checked by looking at the red status LEDs

(light-emitting diodes). When operating correctly, the red status

LEDs should be blinking in unison at a rate of once every

2 seconds. If the red LEDs are not blinking in unison, verify

that correct power is being supplied to all modules. Be sure that

the main base board (MBB) is supplied with the current soft-

ware. If necessary, reload current software. If the problem still

persists, replace the MBB. A red LED that is lit continuously or

blinking at a rate of once per second or faster indicates that the

board should be replaced.
GREEN LED — The MBB has one green LED. The Local

Equipment Network (LEN) LED should always be blinking

whenever power is on. All other boards have a LEN LED

which should be blinking whenever power is on. Check LEN

connections for potential communication errors at the board J3

and/or J4 connectors. Communication between modules is

accomplished by a 3-wire sensor bus. These 3 wires run in

parallel from module to module. The J4 connector on the MBB

provides both power and communication directly to the

marquee display only.
YELLOW LED — The MBB has one yellow LED. The

Carrier Comfort Network (CCN) LED will blink during times

of network communication.

Carrier Comfort Network

®

(CCN) Interface —

The 30MP chiller units can be connected to the CCN if

desired. The communication bus wiring is a shielded,

3-conductor cable with drain wire and is supplied and installed

in the field. See Table 18. The system elements are connected

to the communication bus in a daisy chain arrangement. The

positive pin of each system element communication connector

must be wired to the positive pins of the system elements on

either side of it. This is also required for the negative and

signal ground pins of each system element. Wiring connections

for CCN should be made at LVT. Consult the CCN Contrac-

tor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (Ameri-

can Wire Gage) minimum stranded, tinned copper. Individual

conductors must be insulated with PVC, PVC/nylon, vinyl,

Teflon, or polyethylene. An aluminum/polyester 100% foil

shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,

or Teflon with a minimum operating temperature range of

–20 C to 60 C is required. Wire manufactured by Alpha (2413

or 5463), American (A22503), Belden (8772), or Columbia

(02525) meets the above mentioned requirements.

It is important when connecting to a CCN communication

bus that a color coding scheme be used for the entire network

to simplify the installation. It is recommended that red be used

for the signal positive, black for the signal negative, and white

for the signal ground. Use a similar scheme for cables contain-

ing different colored wires.

At each system element, the shields of its communication

bus cables must be tied together. If the communication bus is

entirely within one building, the resulting continuous shield

must be connected to a ground at one point only. If the commu-

nication bus cable exits from one building and enters another,

the shields must be connected to grounds at the lightning

suppressor in each building where the cable enters or exits the

building (one point per building only). To connect the unit to

the network:

1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white

(ground), and black (–) conductors. (Substitute appropri-

ate colors for different colored cables.)

3. Connect the red wire to (+) terminal on LVT of the plug,

the white wire to COM terminal, and the black wire to the

(–) terminal.

4. The RJ14 CCN connector on LVT can also be used, but is

only intended for temporary connection (for example, a

laptop computer running Service Tool).