DEMAND LIMIT (CCN Loadshed Controlled) — To con-

figure Demand Limit for CCN Loadshed control set the De-

mand Limit Select (Configuration

RSET

DMDC) to 3.

Then configure the Loadshed Group Number (Configura-

tion

RSET

SHNM), Loadshed Demand Delta (Configu-

ration

RSET

SHDL), and Maximum Loadshed Time

(Configuration

RSET

SHTM). See Table 27.

The Loadshed Group number is established by the CCN

system designer. The ComfortLink™ controls will respond to a

Redline command from the Loadshed control. When the

Redline command is received, the current stage of capacity is

set to the maximum stages available. Should the loadshed con-

trol send a Loadshed command, the ComfortLink controls will

reduce the current stages by the value entered for Loadshed

Demand delta. The Maximum Loadshed Time is the maximum

length of time that a loadshed condition is allowed to exist. The

control will disable the Redline/Loadshed command if no

Cancel command has been received within the configured

maximum loadshed time limit.

Cooling Set Point (4 to 20 mA) —

A field supplied

and generated, externally powered 4 to 20 mA signal can be

used to provide the leaving fluid temperature set point. Connect

the signal to LVT-10,8 (+,–). See Table 27 for instructions to

enable the function. Figure 19 shows how the 4 to 20 mA sig-

nal is linearly calculated on an overall 10 F to 80 F range for

fluid types (Configuration

OPT1

FLUD) 1 or 2. The set

point will be limited by the fluid (FLUD) type. Be sure that the

chilled water loop is protected at the lowest temperature.

50% CAPACITY AT 20 mA

75% CAPACITY AT 12 mA

100% CAPACITY AT 4 mA

0

2

4

6

8

10

12

14

16

18

20

DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT

100

80

60

40

20

0

MAX.

ALLOW

ABLE LOAD (%)

Fig. 18 — 4 to 20-mA Demand Limiting

100

(38)

80

(27)

60

(15)

40

(4.4)

20

(-7)

0

(-17)

4

6.3

8.6

10.9

13.1

15.4

17.7

20

4 TO 20 mA SIGNAL TO EMM

SET

POINT

, F (C)

90

(32)

70

(21)

50

(10)

30

(-1)

10

(-12)

(FLUD = 2) MINIMUM
SET POINT 14 F (-10 C)

(FLUD = 1) MINIMUM
SET POINT 38 F (3.3 C)

MAXIMUM
SET POINT
70 F (21.1 C)

Fig. 19 — Cooling Set Point (4 to 20 mA)

EMM

Energy Management Module