Table 21 — Dual Chiller Configuration (Master Chiller Example) (cont)

NOTES:

1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-CCN.
2. Parallel Configuration (PARA) cannot be changed.

Temperature Reset —

The control system is capable of

handling leaving-fluid temperature reset based on return cooler

fluid temperature. Because the change in temperature through

the cooler is a measure of the building load, the return tempera-

ture reset is in effect an average building load reset method.

The control system is also capable of temperature reset based

on outdoor-air temperature (OAT), space temperature (SPT), or

from an externally powered 4 to 20 mA signal. Accessory sen-

sors must be used for SPT reset (33ZCT55SPT) and for OAT

reset (HH79NZ014). The energy management module (EMM)

must be used for temperature reset using a 4 to 20 mA signal.

See Tables 23 and 24.

SUB-MODE

ITEM

KEYPAD ENTRY

DISPLAY

ITEM EXPANSION

COMMENTS

RSET

LLBL

2

LEAD/LAG BALANCE SELECT

CHANGE ACCEPTED

LLBL

LLBD

LEAD/LAG BALANCE DELTA

LLBD

168

LEAD/LAG BALANCE DELTA

DEFAULT 168

LLBD

LLDY

LAG START DELAY

LLDY

5

SCROLLING STOPS

5

VALUE FLASHES

10

SELECT 10

LLDY

10

LAG START DELAY

CHANGE ACCEPTED

LLDY

RSET

PARA

YES

MASTER COMPLETE

ENTER

ESCAPE

ENTER

ESCAPE

ENTER

ENTER

ENTER

ESCAPE

ESCAPE

ENTER

A

B

1/4 N.P.T.

0.505/0.495

0.61
DIA

6” MINIMUM

CLEARANCE FOR

THERMISTOR

REMOVAL

Fig. 14 — Dual Leaving Water Thermistor Well

PART

NUMBER

DIMENSIONS in. (mm)

A B

10HB50106801

3.10 (78.7)

1.55 (39.4)

10HB50106802

4.10 (104.1)

1.28 (32.5)