The Historian Firewall Database and the Historian Proxy Database must be configured so that
the interface is allowed to write data to the Historian Server. See “Modifying the Firewall
Database” and “Modifying the Proxy Database” in the Historian Server manuals.
Note that the Trust Database, which is maintained by the Base Subsystem, replaces the Proxy
Database used prior to Historian version 3.3. The Trust Database maintains all the
functionality of the proxy mechanism while being more secure.
See “Trust Login Security” in the chapter “Managing Security” of the Historian Server
System Management Guide.
If the interface cannot write data to the Historian Server because it has insufficient privileges,
a -
10401
error will be reported in the
pipc.log
file. If the interface cannot send data to a
PI2 Server, it writes a
-999
error. See the section
Appendix A: Error and Informational
for additional information on error messaging.
Historian Server v3.3 and Higher
Security configuration using piconfig
For Historian Server v3.3 and higher, the following example demonstrates how to edit the
Trust table:
C:\PI\adm> piconfig
@table pitrust
@mode create
@istr Trust,IPAddr,NetMask,PIUser
a_trust_name,192.168.100.11,255.255.255.255,piadmin
@quit
For the above,
Trust
: An arbitrary name for the trust table entry; in the above example,
a_trust_name
IPAddr
: the IP Address of the computer running the interface; in the above example,
192.168.100.11
NetMask
: the network mask;
255.255.255.255
specifies an exact match with
IPAddr
PIUser
: the PI user the interface to be entrusted as;
piadmin
is usually an appropriate user