Introduction to the controller, Scope of this manual – Rockwell Automation MinPak Plus DC Drive User Manual User Manual
Page 6
2:1
2: Introduction to the Controller
Scope of This Manual
This manual familiarizes you with
the MinPak Plus DĆC Controller. It
describes receiving, storage,
application, implementation and
installation procedures and
provides an overview of
specifications and operations.
Read this manual in its entirety
before installing and powering the
Controller. Observe all danger
notes, warning notes, and caution
notes; these precautions point out
potentially hazardous procedures
and conditions. All three types of
precautions are enclosed in a box
to call attention to them.
D A DANGER alerts a person that
high voltage is present that
could result in severe bodily
injury or loss of life.
D A WARNING alerts a person to
potential bodily injury if
procedures are not followed.
D A CAUTION alerts a person that
if procedures are not followed,
damage to, or destruction of
equipment could result.
DANGER
ONLY QUALIFIED ELECTRIĆ
CAL PERSONNEL FAMILIAR
WITH THE CONSTRUCTION
AND OPERATION OF THIS
EQUIPMENT AND THE HAZĆ
ARDS INVOLVED SHOULD INĆ
STALL, ADJUST, OPERATE
AND/OR
SERVICE
THIS
EQUIPMENT. READ AND UNĆ
DERSTAND THIS MANUAL IN
ITS ENTIRETY BEFORE PROĆ
CEEDING. FAILURE TO OBĆ
SERVE THIS PRECAUTION
COULD RESULT IN SEVERE
BODILY INJURY OR LOSS OF
LIFE.
MinPak Plus SingleĆPhase DĆC Controller Specifications
Input Voltage and Frequency Ratings:
Nominal Line Voltage
115 or 230 VAC
. . . . . . . . . . . . . . . . . . . . . .
Number of Phases
Single
. . . . . . . . . . . . . . . . . . . . . . . . .
Voltage Variation
+ 10% of Nominal
. . . . . . . . . . . . . . . . . . . . . . . . . .
Nominal Line Frequency
50 or 60 cycles
. . . . . . . . . . . . . . . . . . . .
Frequency Variation
+ 2 cycles of Nominal
. . . . . . . . . . . . . . . . . . . . . . . .
AĆC Line Fault Ampacity:
Allowable AĆC Line Symmetrical
1,000 or (horsepower dependent)
. . . . . . . . . . . . .
Fault Current (RMS)
5000 amps (with NEC or CEC approved external disconnect)
. . . . . . . . . . . . . . . . . . . . . . . .
(See Table 2Ć1).
AĆC Line KVA:
Maximum Source KVA
(See Table 2Ć1)
. . . . . . . . . . . . . . . . . . . . .
Multiple Drives per Line
Maximum 3 Drives per Line
. . . . . . . . . . . . . . . . . . . . .
Minimum Source KVA
(See Table 2Ć1)
. . . . . . . . . . . . . . . . . . . . . .
DĆC Voltage Ratings:
115 VAC Line:
Armature Voltage
90 VDC
. . . . . . . . . . . . . . . . . . . . . . . .
Field Voltage
50 or 100 VDC
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
230 VAC Line:
Armature Voltage
180 VDC
. . . . . . . . . . . . . . . . . . . . . . . .
Field Voltage
100 or 200 VDC
. . . . . . . . . . . . . . . . . . . . . . . . . . . .