beautypg.com

Rockwell Automation MinPak Plus DC Drive User Manual User Manual

Page 41

background image

5:10

Verify that the run/jog switch is in propĆ

er position.

Is the run/jog

switch in the

run position?

Check between terminals 35 and

PIn 139 (COMMON) for 24 VDC.

Is 24VDC

present?

Replace the regulator board.

Fixed?

See Note #1

End

Start

Yes

Place the run/jog

switch in the run poĆ

sition.

Fixed?

Done

No

Yes

Yes

No

No

Note: #1: Contact local sales/service office.

**

*

*Reference the layout of the regulator board for PIN location.

**The center arm switch should go to PIN 35 and the run

position of the switch should connect to the common point

between the start/stop pushbutton.

Done

Check the wiring of

the run/jog switch to

the regulator board.

Is there

continuity between

the run/job switch

and the regulator

board

connections?

Correct problem

Fixed?

Done

Yes

No

Replace the

run/jog switch

Fixed?

Done

Yes

No

Yes

No

No

Yes

DANGER

SOME OF THE FOLLOWING CHECKS AND PROCEDURES REQUIRE THE POWER TO BE ON. EXERCISE

EXTREME CARE AS HAZARDOUS VOLTAGE EXISTS. FAILURE TO OBSERVE THIS PRECAUTION COULD

RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.

Figure 5Ć7. M" Contactor PicksĆUp But Only Remains in as Long as the Start Button is Pushed.