3: Install and Wire The Drive
DANGER
ONLY QUALIFIED ELECTRIĆ
CAL PERSONNEL FAMILIAR
WITH THE CONSTRUCTION
AND OPERATION OF THIS
EQUIPMENT AND THE HAZĆ
ARDS INVOLVED SHOULD
INSTALL, ADJUST, OPERATE
AND/OR
SERVICE
THIS
EQUIPMENT.
READ AND
UNDERSTAND THIS MANUAL
IN ITS ENTIRETY BEFORE
PROCEEDING. FAILURE TO
OBSERVE THIS PRECAUTION
COULD RESULT IN SEVERE
BODILY INJURY OR LOSS OF
LIFE.
DANGER
THE USER IS RESPONSIBLE
FOR CONFORMING TO THE
NATIONAL
ELECTRICAL
CODE (NEC) AND ALL OTHER
APPLICABLE LOCAL CODES
WITH RESPECT TO WIRING
PRACTICES,
GROUNDING,
DISCONNECTS, AND OVERĆ
CURRENT PROTECTION ARE
OF
PARTICULAR
IMPORĆ
TANCE.
FAILURE TO OBĆ
SERVE THIS PRECAUTION
COULD RESULT IN SEVERE
BODILY INJURY OR LOSS OF
LIFE.
DANGER
THIS EQUIPMENT IS AT LINE
VOLTAGE WHEN AĆC POWER
IS CONNECTED. DISCONĆ
NECT AND LOCKOUT ALL
UNGROUNDED
CONDUCĆ
TORS OF THE AĆC POWER
LINE. FAILURE TO OBSERVE
THIS PRECAUTION COULD
RESULT IN SEVERE BODILY
INJURY OR LOSS OF LIFE.
General
This Section outlines the
procedures that are to be followed
to properly install the MinPak Plus
SingleĆPhase DĆC Drive. Refer to
Figure3Ć2 for mounting dimensions.
Install the Controller -
Panel Layout
The controller is designed as a wall
or panel mount unit and must be
hung within 10_ of vertical with the
rear of the chassis firmly bolted to
themounting surface. Do not mount
thechassis in a horizontal position.
Reference figures 3Ć1, 3Ć1A and
3Ć1B for minimum mounting
distances and/or mounting
orientations.
Leave 2 inches (50 mm) clearance
around the 3 unhinged sides of the
chassis. This area must remain
unobstructed for proper air
circulation through theheat sink. Do
not placethecontroller directly in a
corner, leave at least 8 inches (200
mm) from thetop and 6 inches (150
mm) from thebottom of thecabinet.
Regardless of the above placement
guidelines, the user is responsible
for ensuring that the Controller's
ambient specification of 0 to 55_C is
met. Relative humidity must be kept
within 5% to 95% without
condensation.
Figure 3Ć1. Enclosure Mounting
Minimum Distances
Figure 3Ć1A. Open Panel Minimum
Mounting Distances
Figure 3Ć1B. Mounting
Orientations