Chapter 7 register map, P.000, P.001 – Rockwell Automation GV3000/SE AC Drive ControlNet Network Communication Board, M/N 2CN3000 User Manual
Page 91: P.002, P.003, P.004, P.005, P.006, P.007, P.008
Register Map
7-1
C
HAPTER
7
Register Map
Table 7.1 – File N10:X (Drive Read/Write Parameters)
File
Address
Parameter Name
Parameter
Number
Type
Notes
N10:0
Control Source
P.000
Configurable 0 = Front Panel (Local)
1 = Terminal strip
2 = Option Port (Network)
3 = Serial Port (PC-host)
N10:1
Accel Time 1 (RAMP 1)
P.001
Tunable
1 = 0.1 sec
N10:2
Decel Time 1 (RAMP 1)
P.002
Tunable
1 = 0.1 sec
N10:3
Minimum Speed
P.003
Tunable
50 = 5.0 Hz / 150 = 150 RPM
N10:4
Maximum Speed
P.004
Tunable
50 = 5.0 Hz / 150 = 150 RPM
N10:5
Current Limit
P.005
Tunable
100 = 100%
N10:6
Second Menu Password
P.006
Tunable
Note 1
N10:7
Term Strip Dig Inputs Config
P.007
Configurable 0 through 12
N10:8
Term Strip Spd Ref Source
P.008
Configurable 0 through 7
N10:9
Term Strip Anlg In Offset
P.009
Tunable
100 = 100
N10:10
Term Strip Anlg In Gain
P.010
Tunable
1000 = 1.000
N10:11
Term Strip Anlg In Configure
P.011
Configurable 0 through 7
N10:12
Term Strip Anlg Out Source
P.012
Tunable
0 through 3
N10:13
Output Relay Configuration
P.013
Configurable 0 through 3
N10:14
Trim Reference Source
P.014
Configurable 0 through 3
N10:15
Trim Gain Percentage
P.015
Tunable
999 = 99.9%
N10:16
Draw Gain Percentage
P.016
Tunable
999 = 99.9%
N10:17
Accel Time 2 (RAMP 2)
P.017
Tunable
1 = 0.1 sec
N10:18
Decel Time 2 (RAMP 2)
P.018
Tunable
1 = 0.1 sec
N10:19
S-Curve Enable
P.019
Configurable 0 = off; 1 = on
N10:20
Jog Speed Reference
P.020
Tunable
50 = 5.0 Hz / 150 = 150 RPM
N10:21
Jog Ramp Accel Time
P.021
Tunable
1 = 0.1 sec
N10:22
Jog Ramp Decel Time
P.022
Tunable
1 = 0.1 sec
N10:23
MOP Accel/Decel Time
P.023
Tunable
1 = 0.1 sec
N10:24
MOP Reset Configuration
P.024
Tunable
0 to 2
N10:25
Stop Type
P.025
Tunable
0 = Coast; 1 = Ramp
Note 1: This parameter cannot be changed from the ControlNet network, or it is reserved. When writing to this parameter, use
a value of 0. When you read this parameter, you receive a value of 0.