Register Map

7-1

C

HAPTER

7

Register Map

Table 7.1 – File N10:X (Drive Read/Write Parameters)

File

Address

Parameter Name

Parameter

Number

Type

Notes

N10:0

Control Source

P.000

Configurable 0 = Front Panel (Local)

1 = Terminal strip

2 = Option Port (Network)

3 = Serial Port (PC-host)

N10:1

Accel Time 1 (RAMP 1)

P.001

Tunable

1 = 0.1 sec

N10:2

Decel Time 1 (RAMP 1)

P.002

Tunable

1 = 0.1 sec

N10:3

Minimum Speed

P.003

Tunable

50 = 5.0 Hz / 150 = 150 RPM

N10:4

Maximum Speed

P.004

Tunable

50 = 5.0 Hz / 150 = 150 RPM

N10:5

Current Limit

P.005

Tunable

100 = 100%

N10:6

Second Menu Password

P.006

Tunable

Note 1

N10:7

Term Strip Dig Inputs Config

P.007

Configurable 0 through 12

N10:8

Term Strip Spd Ref Source

P.008

Configurable 0 through 7

N10:9

Term Strip Anlg In Offset

P.009

Tunable

100 = 100

N10:10

Term Strip Anlg In Gain

P.010

Tunable

1000 = 1.000

N10:11

Term Strip Anlg In Configure

P.011

Configurable 0 through 7

N10:12

Term Strip Anlg Out Source

P.012

Tunable

0 through 3

N10:13

Output Relay Configuration

P.013

Configurable 0 through 3

N10:14

Trim Reference Source

P.014

Configurable 0 through 3

N10:15

Trim Gain Percentage

P.015

Tunable

999 = 99.9%

N10:16

Draw Gain Percentage

P.016

Tunable

999 = 99.9%

N10:17

Accel Time 2 (RAMP 2)

P.017

Tunable

1 = 0.1 sec

N10:18

Decel Time 2 (RAMP 2)

P.018

Tunable

1 = 0.1 sec

N10:19

S-Curve Enable

P.019

Configurable 0 = off; 1 = on

N10:20

Jog Speed Reference

P.020

Tunable

50 = 5.0 Hz / 150 = 150 RPM

N10:21

Jog Ramp Accel Time

P.021

Tunable

1 = 0.1 sec

N10:22

Jog Ramp Decel Time

P.022

Tunable

1 = 0.1 sec

N10:23

MOP Accel/Decel Time

P.023

Tunable

1 = 0.1 sec

N10:24

MOP Reset Configuration

P.024

Tunable

0 to 2

N10:25

Stop Type

P.025

Tunable

0 = Coast; 1 = Ramp

Note 1: This parameter cannot be changed from the ControlNet network, or it is reserved. When writing to this parameter, use

a value of 0. When you read this parameter, you receive a value of 0.