Step 5.3 100 to 150 HP drives only: Align the Power Module Interface board on the
eight plastic standoffs on the back of the mounting panel. Carefully press it
into place. Make sure that good contact has been made with the two
grounding standoffs.
Step 5.4 Route the Regulator board’s 60-conductor ribbon cable through the slot in
the hinged mounting panel to the connector on the Power Module Interface
board. Align the two connectors. Place your thumb beneath the Power
Module Interface board for support and carefully press the ribbon cable
connector in until it locks into position.
Step 5.5 Swing the hinged mounting panel back into position. Make sure no wires or
cables are pinched by the panel.
Step 5.6 Refasten the two screws at the top of the panel.
Step 5.7 Route the Network Drop Cable through the right-most opening at the
bottom of the drive, away from the AC lines.
Step 5.8 Connect the brown wire to terminal 1 of the 2-connector terminal strip.
Connect the white wire to terminal 2.
Step 5.9 Reconnect any wiring that was removed from the Regulator board.
Step 5.10 Replace mounting panel and fasten with two screws at the top of the hinged
panel (where the keypad bracket is mounted).
Step 5.11 NEMA 4X/12 drives only: Before installing the cover, check that the gaskets
on the cover are flat and within the gasket channels.
Step 5.12 Reinstall the cover with the six screws removed in step 1.3. Make sure no
wires or cables are pinched by the cover.
To maintain the integrity of NEMA 4X/12 drives, sequentially tighten the six
cover screws to ensure even compression of the gaskets. Do not exceed
2.2 Nm (20 in-lb) of torque on these screws.