beautypg.com

30v20xx, 100v20xx, 40v20xx – Rockwell Automation GV3000/SE AC Drive ControlNet Network Communication Board, M/N 2CN3000 User Manual

Page 28: 100v40xx, 50v20xx, 125v40xx, 60v20xx, 150v40xx, 75v20xx, 200v40xx

background image

2-16

GV3000/SE AC Drive ControlNet Network Communication Option Board

2.4

Installing the ControlNet Option Board in
30 to 100 HP @ 230 VAC and 75 to 200 HP@460 VAC
Drives

Use this procedure to install the ControlNet option board in the drives listed in
table 2.4.

Unless otherwise indicated, keep all hardware that is removed. You will need it for
reassembly. This includes screws, lock washers, and rivets.

Important: Read and understand the warning labels on the outside of the drive

before proceeding.

!

ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and
understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in
severe bodily injury or loss of life.

ATTENTION: The drive is at line voltage when connected to incoming
AC power. Disconnect, lock out, and tag all incoming power to the drive
before performing the following procedure. Failure to observe this
precaution could result in severe bodily injury or loss of life.

ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait five
minutes for the DC bus capacitors to discharge and then check the
voltage with a voltmeter to ensure the DC bus capacitors are discharged
before touching any internal components. Failure to observe this
precaution could result in severe bodily injury or loss of life.

ATTENTION: The drive contains ESD- (Electrostatic Discharge)
sensitive parts and assemblies. Static control precautions are required
when installing, testing, servicing, or repairing the drive. Erratic machine
operation and damage to, or destruction of, equipment can result if this
procedure is not followed. Failure to observe this precaution can result
in bodily injury.

Table 2.4 – Model Numbers for 30 to 100 HP @ 230 VAC and 75 to 200 HP@460 VAC Drives

30V20xx

100V20xx

40V20xx

100V40xx

50V20xx

125V40xx

60V20xx

150V40xx

75V20xx

200V40xx

75V40xx