8-2
GV3000/SE AC Drive ControlNet Network Communication Option Board
8.2
Communication Error Codes
Table 6.3 defines the error codes that are returned by the drive for Typed Read and
Typed Write messages.
Table 8.2 – Communications LEDs
LED State
Probable Cause
Recommended Action
Off
No power
Turn power on
Steady Red (A & B)
Faulted unit
Cycle power. If the fault persists, contact your Reliance
Electric representative.
Alternating
Red/Green (A & B)
Self test
None
Alternating
Red/Off (A & B)
Incorrect node configuration
Check the network address and other ControlNet
configuration parameters.
Off
Channel disabled
None; configure for communication.
Steady Green
Normal operation
None
Flashing Green/Off
Temporary error
Node is not configured
Verify that the node number has been set.
Check that the cable is properly terminated.
Verify that the config manager node is working.
Flashing Red/Off
Media Fault
No other nodes present on
the network
This channel’s cable is not
as good as the other.
Check media for problems.
Add other nodes to the network.
Never remove the green channel if the other is red;
communication may be lost.
Flashing
Red/Green
Incorrect network
configuration
Cycle power. If the fault persists, contact your Reliance
Electric representative.
Table 8.3 – Communication Error Codes
Status
Description
ControlLogix
™
PLC-5
Error
Extended Error
Error
0
0
0
No Error
00F0
0002
-4094 (0xF002) Incomplete address
00F0
0003
-4093 (0xF003) Incorrect address
00F0
0006
-4090 (0xF006) Addressed file does not
exist in target processor
00F0
0007
-4089 (0xF007) Destination file is too small
for number of words
requested
00F0
000B
-4085 (0xF00B) Privilege error, access
denied
00F0
000C
-4084 (0xF00C) Requested function is not
available
00F0
0011
-4079 (0xF011) Data type requested does
not match available