AutoMax Remote I/O Head M/N 57C328
and M/N 57C330
Ambient Conditions
D Storage Temperature: -40_C to 85_C
-40_F to 185_F
D Operating Temperature: 0_C to 60_C
32_F to 140_F
D Humidity: 5 to 95%, nonĆcondensing
D Altitude: 1000 meters (3300 feet) without derating
Dimensions
Without Cables
With Cables Attached
D Height:
23.9 cm (9.40 inches)
23.9 cm (9.40 inches)
Width:
14.0 cm (5.50 inches)
14.0 cm (5.50 inches)
Depth:
19.2 cm (7.55 inches)
24.1 cm (9.50 inches)
Weight
D 2.9 kilograms (6.5 pounds)
Input Power
D 120 VAC (-15% to +10%) (102Ć132 VAC)
D 240 VAC (-15% to +10%) (204Ć264 VAC)
Holdup Time
D 3 Cycle
Line Frequency
D 47.5 to 63 Hz
Momentary Voltage Deviation (60 Millisecond Duration)
D 120 VAC (+30%) (80Ć150 VAC)
D 240 VAC (+30%) (160Ć300 VAC)
Maximum Load
D at 120 VAC: 0.5A
D at 240 VAC: 0.25A
Maximum Power Dissipation
D 50 W
Fuse Type
D Bussr 2 Amp, 250V, AGC, or equivalent
Ready Relay Contact Rating
D 8A, 250 VAC