Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual
Page 19

2Ć5
Note that during powerĆup diagnostics, the bottom four LEDs (CPU,
READY, FAULTMSB, FAULTLSB, and RAIL FAULT) will stay on long
enough to allow verification that they will light.
0
1
2
3
L1
L2
120
240
FUSE TYPE
250V
AGC 2 AMP
RUN
POWER
FAULT MSB
FAULT LSB
CPU READY
RAIL FAULT
REMOTE
I/O HEAD
AutoMaxR
Figure 2.3 Ć AutoMax Remote I/O Head Faceplate (M/N 57C328 and M/N 57330)
2.1.4
Remote I/O Head (M/N 57C330)
The Remote I/O Head can be used as an interface between the
AutoMax Remote I/O network and the AutoMate rail I/O system,
which consists of Local Heads, digital or analog rails, LED modules,
or Thumbwheel Switch modules. Note that although the Remote I/O
Head can be used as an interface to drives with railĆtype interface
ports (such as the Reliancer GPĆ2000/VTAC V controller), it is
recommended that only the Remote Drive Interface Head
(M/N 57C329) be used for interfacing with drives over an AutoMax
Remote I/O network. See section 2.1.5 for more information.