5Ć6
where:
PORT
=
0Ć3
REGISTER =
0Ć3
I/O
= `
Ć No rail exists
`unknown' Ć Rail exists but it has not been
determined whether it is INPUT or
OUTPUT (M/N 57C330 only)
`INPUT'
Ć Rail exists and contains INPUT
modules
`OUTPUT'
Ć Rail exists and contains OUTPUT
modules
`INPUT/
OUTPUT'
Ć Rail exists (M/N 57C328 only)
5.2.3
Clear (C)
The Clear command is used to clear the twoĆdigit LAST RESET code
and the PORT RETRIEScounters. When C" is entered, CLEARED"
will be displayed for the LAST RESET and PORT RETRIES fields.
5.2.4
Read Port (R)
The Read Port command is used to read the registers on a rail
attached to the Head. When R" is entered, you will be prompted for
a port number. When the port number (0Ć3, followed by a carriage
return) is entered, the data from that particular port will be displayed.
Data will be displayed in hexadecimal, decimal, and binary format:
REGISTERąI/OąHEXąDECąBIN
5.2.5
Write Port (W)
Entering W" enables you to write data to an output rail or an output
register on a drive. This command is valid only when the serial line is
inactive. Data can be written in decimal (default format), in
hexadecimal, or in binary.
WARNING
BEFORE PERFORMING THE WRITE SLOT COMMAND, THE USER MUST VERIFY
THAT THE OUTPUTS ARE EITHER ELECTRICALLYDISCONNECTED OR WILL
NOT CAUSE UNEXPECTED MACHINE MOTION IF ENERGIZED. FAILURE TO
OBSERVE THESE PRECAUTIONS COULD RESULT IN BODILYINJURY.
You must respond to the following prompts:
WRITE PORT: Enter the port number (0Ć3) followed by a carriage
return.
REGISTER: Enter the register number (0 to 3) followed by a
carriage return.
At this point, if the entered rail location cannot be written to because
the register does not exist or the rail is an input rail, the appropriate
error message will be displayed and the operation will be terminated.