Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual
Page 133

KĆ15
Step 4.
Disconnect the twistedĆpair cable from the transceiver's
fourĆscrew terminal block.
Step 5.
Loosen the captive screws on the transceiver's faceplate
and remove it from the rack.
Step 6.
If the new transceiver is to be located at an extreme end
of the rack, connect the jumper between terminals 3 and
4 on the transceiver's sixĆscrew terminal block.
Step 7.
Insert the transceiver into the rack and secure it with the
captive screws.
Step 8.
Connect the twistedĆpair cable to the new transceiver as
shown in section K2.3.
Step 9.
Connect the fiberĆoptic cable as shown in section K2.5.
Step 10. Turn the Power Supply on. Verify that the LED on the
faceplate of the transceiver is on. This indicates that it is
receiving power.
Step 11. ReĆattach the plastic panel to the front of the rack.
L2.8
Replacing the FiberĆOptic Rack and Power
Supply
Use the following procedure to replace the FiberĆOptic Rack and
Power Supply. Before beginning this procedure, verify that the
fiberĆoptic cable, the RackĆMounted Transceiver, and its
corresponding StandĆAlone Transceiver are labeled with the network
ID number, the network drop number, and the Remote I/O module
slot number.
Step 1.
Remove the plastic panel from the front of the FiberĆOptic
Rack.
Step 2.
Turn the FiberĆOptic Rack's Power Supply off using the
rocker switch on the Power Supply's faceplate.
Step 3.
Remove power from the Power Supply's external 115 or
230VAC source.
Step 4.
Disconnect the Power Supply's power cord from the
external 115 or 230VAC source.
Step 5.
Disconnect the twistedĆpair cables and fiberĆoptic cables
from each transceiver in the rack.
Step 6.
Remove the rack from the mounting surface.
Step 7.
Set the selector switch on the back of the new rack to 115
or 230 VAC as required.
Step 8.
Attach the rack to the mounting surface.
Step 9.
Insert each transceiver into the new rack and connect the
twisted pair cable (refer to section K2.3) and fiberĆoptic
cable (refer to section K2.5).
Step 10. Connect the power cord to the 115 or 230VAC source.
Step 11. Turn power on to the 115 or 230VAC source.
Step 12. Turn the FiberĆOptic Rack's Power Supply on using the
rocker switch on the Power Supply's faceplate. The
builtĆin indicator in the switch will illuminate to indicate the
presence of power. Verify that the LEDs on all of the
RackĆMounted Transceivers in the rack are on.