Rockwell Automation 2706-P42_P43_P44_P72_P74_P92_P94 InView Marquee Message Display User Manual User Manual
Page 99

Publication 2706-UM016D-EN-P - March 2006
InView Protocol 4-33
Add/Remove a Message using a Modbus ASCII 10 Frame Query
(Recommended)
This method uses both registers 40101 and 40102 in the display to add
and remove a message from the message queue respectively. By using
the Guaranteed mode, only the display that is addressed on the
network accepts and processes the information it receives. The
following is an example of adding message #0015 and removing
message #0045 from the message queue on display number 019.
Transmission:
Query for Add/Remove a Message
Response:
The normal response to a function 10 is to echo the address, function
code, starting address and the number of registers that were loaded.
Response for Add/Remove a Message
Add/Remove a Message using Modbus ASCII 10 Frame
Transmission
This method uses both registers 40101 and 40102 in the display to
activate and de-activate messages respectively. By using the Broadcast
mode, all displays on the network will accept and process the
Beginning
of Frame
ADDR
FUNC
H.O.
ADDR
L.O.
ADDR
QUANTITY
BYTE CNT
DATA
:
13
10
00
64
0002
04
000F 002D
LRC
Error
EOF
Ready
to rec.
resp
37
CR
LF